User’s Manual for
CyberShield
CBN50U48A-1
CyberShield UPSs are designed to provide a local power solution for
cable telephony, wireless local loop (WLL), and fiber to the home
(FTTH) broadband equipment.
ENCLOSURE INSTALLATION
Carefully follow these instructions during installation of this device:
1.) Carry out the installation in a safe area that is free of excessive dust and has adequate airflow.
2.) Screws must be appropriate for total weight of the UPS and the mounting surface material.
3.) Do not operate the UPS where the temperature and humidity are outside the specified limits.
(Refer to specification in this manual.)
BATTERY REPLACEMENT
This battery is hot-swappable. As long as utility power is on , you may leave the UPS and connected
equipment on while replacing a new battery.
Once the battery is disconnected, the connected equipment is not protected from power
outages.
Deliver spent batteries to a recycling facility or ship to the manufacturer in the
replacement battery packing material.
WARNING INDICATOR
OPERATION
Connect: Equipment and Power
Step1. Plug the UPS power cord into the utility power cord inlet
Step2. Plug the UPS power cord into the wall outlet.
COLD START
The cold start feature is for applying power to the UPS and connected equipment when the UPS is
off and there is no utility power. Before using the cold start feature, please make sure the battery is
charged. To start the cold start feature, press the recessed cold start button with a small pointed
object.
UPS is on utility power.
UPS is on battery power.
DC output power is provided by the battery or
utility power.
The battery is not connected or the battery
needs to be replaced.
Green
Yellow
Green
Red
Indicator
Step 1:
a. Remove the battery cover.
Step 2:
a. Unstrap strap from battery.
b. Slide battery off of the shelf.
c. Disconnect battery cable
connector at chassis end.
Step 3:
a. Use the enclosed installation template to
mark an installation location for the unit.
b. Mount the unit on the wall with 2 mounting
screws into the keyhole slots.
c. Tighten the screws to secure the units.
d. Connect the battery connector and put
the battery back.
Step 1:
a. Remove the battery cover.
Step 2:
a. Loosen the battery strap.
b. Disconnect battery cable connector
to remove battery.
c. Replace with new battery and
re-connect the battery connector.
Step 3:
a. Tighten the battery strip and
close the battery cover.
Front Panel
AC
OUTPUT
BATTERY
Note: please always mount the unit on the wall when it is working.
AC OUT PUT B AT TER Y
Back Panel
Color Condition
IMPORTANT SAFETY WARNINGS
(SAVE THESE INSTRUCTIONS)
This manual contains important instructions regarding the installation and operation of this device.
Read this manual thoroughly before attempting to unpack , install or operate this device.
CAUTION! The battery can energize hazardous live parts inside even when the AC input power is
disconnected.
CAUTION!
To reduce the risk of fire or electric shock, install in a temperature and humidity
controlled indoor area, free of conductive contaminants. To find the acceptable
temprature and humidity ranges,please refer to the device specifications.
CAUTION!
To reduce the risk of electric shock, keep the cover on. there are no user serviceable
parts inside the unit, including the battery. Please contact us or our dealer for service.
CAUTION! When replacing batteries, the replacement should have the same rating:
Listed/Certified Valve Regulated Lead Acid Battery, 12V, max. 20Ah.
CAUTION! Before replacing batteries, remove conductive jewelry, such as chains, watches and rings,
and use tools with insulated handles. High energy passed through conductive materials
can cause severe burns.
CAUTION! Don’t dispose of batteries in a fire. Batteries may explode if improperly disposed.
Recycle batteries in accordance with local regulations.
The UPS battery is charging when it’s connected to utility power. The battery is charging
during its first 24 hours of normal operation. Don’t expect full battery capacity during this
initial charging period.
CAUTION!
CAUTION! It is recommended to connect the unit to the required equipment and battery before
plugging in the utility power.
CAUTION! Runtimes based on testing fully-charged, new batteries at normal operating conditions.
Runtime curve is approximate and varies based on battery age, level of charge at test,
environment, and other variables.
CAUTION! To avoid electric shock, unplug power cable from the AC power source before servicing
the battery or installing a computer component.
The battery must be supplied by CyberPower. Using improper battery which is not
evaluated with this model could cause a risk and is at the user's own risk.
CAUTION!
Mounting Surface
1"~1.5"
1/8"
1/4"
17/32"
RECOMMENDED SCREW SIZE
SPECIFICATION
48V
48V RTN
SIG RTN
ON BATTERY
REPLACE BATTERY
BATTERY MISSING
LOW BATTERY
+ Voltage output
- Voltage output
Signal return
Low when operating from utility line.
Open when operating from battery.
Low when battery is charged.
Open when battery fails the Self Test.
Low when battery is present.
Open when battery is missing.
Low when battery is near full charge capacity.
Open when operating from a battery with < 20% capacity.
Signal Message
MODEL
Input Voltage Range
Input Frequency Range
Input Power Cord
AC Input
CBN50U48A-1
Standard NEMA1-15P
2-Prong Power Cord
90- 264VAC
50 - 60 Hz
(L*W*D)
On Battery Output Voltage
Continuous Power Capability
Output Power Max
E ficiency (at Full Load, 25°C )f
Battery Type
Numbers of Battery
Typical Recharge Time (25°C)
Replaceable
Lightning / Surge Protection
Audible Indicator
LED Indicators
Auto-Charge
Communication Interface
Maximum Dimensions
Weight
Operating Temperature
Operating Humidity
Max Operating Elevation
Max Storage Elevation
Storage Temperature
Environment
Battery
DC Output
Physical
Surge Protection and Filtering
Warning Diagnostics
Management
48VDC
50W
50W
20AH / 12V x 1
30cm x 28cm x 10.1cm
7.9Kg
Sealed, Maintenance Free Lead-Acid Battery
On Battery, Replace Battery, Battery Missing, Low Battery
32°F - 104°F (0°C - 40°C)
10,000 ft (3,048m)
Utility Failure, Low Battery
50,000 ft (15,240m)
5°F - 113°F (-15°C - 45°C)
>85%
Around 38 hours (90% Charged)
Yes
Yes
AC, Output, Battery
Yes
0 - 95% noncondensing within enclosure
COMMUNICATION SIGNALS
Utility Power Cord Inlet
Communication signals
LIMITED WARRANTY
CyberPower warrants to you, the Initial Purchaser, that the Product will be free from defects in material and workmanship for three years from the date of original purchase, subject to the terms of this Limited
Warranty. This Limited Warranty gives you specific rights, and you may have other rights, which vary from State to State or Province to Province.
Any Implied Warranty of Merchantability or for Fitness for a Particular Purpose, if applicable to the Product, is limited in duration to three years. This provision shall NOT create any Implied Warranty or
Merchantability or of Fitness for a Particular Purpose that would not otherwise apply to the Product. NOTE: Some States and Provinces do not allow limitations on how long an implied warranty lasts,
so the above limitation may not apply to you.
To be covered you must still be the owner of the Product at the time of the failure that results in the claim made under this Limited Warranty. Your sole and exclusive remedies are those provided by this
Limited Warranty. This exclusion of other express warranties applies to written and oral express warranties. CyberPower excludes any liability for personal injury. CyberPower excludes any liability for direct,
indirect, special, incidental, or consequential damages, whether for damage to or loss of property, loss of profits, business interruption, information or data. This exclusion applies even though damage or loss
is caused by negligence or other fault. NOTE: Some States or Provinces do not allow the exclusion or limitations of incidental or consequential damages, so the above limitation may not apply to you.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT OR OTHER HIGH RISK ACTIVITIES.
CyberPower does not sell the PRODUCT for use in high-risk activities. The PRODUCT is not designed or intended for use in hazardous environments requiring fail-safe performance, including the operation
of nuclear facilities, aircraft navigation or communication systems, air traffic control, weapons systems, life support or medical applications or for use in any circumstance in which the failure of the PRODUCT
could lead directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical or life support device (collectively, "High Risk Activities").
CyberPower expressly disclaims any express or implied warranty of fitness for High Risk Activities. CyberPower does not authorize use of any PRODUCT in any High Risk activities.
ANY SUCH USE IS IMPROPER AND IS A MISUSE OF A CYBERPOWER PRODUCT.
The Limited Warranty is governed by the laws of the United States and the State of Minnesota, without reference to conflict of law principles. The application of the United Nations Convention of Contracts for
the International Sale of Goods is expressly excluded
FCC NOTICE:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with these instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: (1) Reorient or relocate the receiving antenna.
(2) Increase the separation between the equipment and receiver. (3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. (4) Consult the dealer or an
experienced radio/TV technician for help.
CAUTION: Shielded signal cables must be used with this device to ensure compliance with Class B FCC limits.
CAUTION: Any changes or modifications not expressly approved by CyberPower could void the authority granted by the FCC to operate this equipment.
For more information, please contact:
CyberPower Systems ( USA ), Inc. 4241 12th Avenue East, Suite 400, Shakopee, MN 5537 9 Phone: (952)403-9500 Fax: (952)403-0009 cyberpowersystems.com
CyberPower Systems ( EUROPE ), Inc.. Flight Forum 3545, 5657DW Eindhoven, The Netherlands E-mail: sales@cyberpower-eu.com eu.cyberpowersystems.com
K01-5048001-00
The communication signals of this unit are isolated from the internal circuitry via open
collector opto-coupled transistors. The connection “SIG RTN” (Signal Return) is a common
return point for all communication signals. In the typical application, the attached equipment
digital ground connects to Signal Return, and pull-up resistors turn the open collector
signals into logic levels.
REPLACE BATTERY
BATTERY MISSING
LOW BATTERY
-
SIG RTN
ON BATTERY
12V
XBP
COLD START
48V RTN
+
48V
WARNING: Cancer and Reproductive Harm-
www.P65Warnings.ca.gov.


Produktspezifikationen

Marke: CyberPower
Kategorie: UPS
Modell: CyberShield CBN50U48A-1

Brauchst du Hilfe?

Wenn Sie Hilfe mit CyberPower CyberShield CBN50U48A-1 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung UPS CyberPower

Bedienungsanleitung UPS

Neueste Bedienungsanleitung fĂĽr -Kategorien-