CLT- & CLX-4HSW4
Functional Summary NOTE: Modules and terminal blocks must be installed
into the lowest available spaces and continue toward the
top of the enclosure.
The Crestron 4-Feed, 4-High Switch Terminal Block and
Module (CLT-4HSW4 and CLX-4HSW4, respectively),
are considered a single entity and must be used together.
They ship separately to permit termination of the field
wiring to the CLT-4HSW4 prior to installation of the
CLX-4HSW4, as described in this guide. They can be
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to
terminate four circuit feeds (LINE and NEUTRAL) and
distribute the controlled circuits (LOAD) to the fixtures.
The module connects to the terminal block and performs
switching (non-dim) control of four incandescent, low
voltage, neon, cold cathode, fluorescent, or HID lighting
loads, or motor loads. The maximum load is 16 amps (1/2
HP) for each controlled circuit (64 amps total per
module). The unit requires 120VAC 60 Hz input voltage.
An oversize heat sink dissipates heat efficiently. There are
LEDs on the module to indicate communication to a
Cresnet network, input power to the module, and output
power to the load.
Terminal Block & Module Locations (Single-wide Enclosure)
MODULETERMINAL
BLOCK
GROUNDING
TERMINAL
BLOCK
Industry Compliance
This product is Listed to applicable UL Standards and
requirements by Underwriters Laboratories Inc.
Terminal Block & Module Locations (Double-wide Enclosure)
(E103692)
GROUNDING TERMINAL BLOCKS
MODULETERMINAL BLOCK
(LEFT)
TERMINAL BLOCK
(RIGHT)
Installation
Terminal block and module must be mounted into a
Crestron Automation Enclosure by a licensed electrician,
in accordance with all national and local codes.
CAUTION: This equipment is for indoor use only and
needs to be air-cooled. Mount in a well-ventilated area.
The ambient temperature must be 32°F to 104°F (0°C to
40°C). The relative humidity must be 0% to 90% (non-
condensing).
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and
right sides) of double-wide enclosures. Modules are
installed along the right side of single-wide enclosures
and side-by-side in the center of double-wide enclosures.
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so
that they can be properly wired. Refer to the illustrations
shown in the next column when considering the location
of terminal blocks and modules within an enclosure.
Crestron Electronics, Inc. Installation Guide – DOC. 5986C
15 Volvo Drive Rockleigh, NJ 07647 (2002068)
Tel: 888.CRESTRON 11.06
Fax: 201.767.7576 Specifications subject to
www.crestron.com change without notice.
Terminal Block & Module Crestron CLT- & CLX-4HSW4
5. Grounding terminal blocks are available in the
cabinet for termination of ground wires. Tighten
to 35 in-lbs. (14 – 10 AWG), 40 in-lbs.
(8 AWG), or 45 in-lbs. (6 – 4 AWG).
NOTE: Unless otherwise indicated, the lighting system
specified in this guide is modular, requiring assembly in
the field by a licensed electrician, in accordance with all
national and local codes.
6. Test each circuit for electrical faults by turning
on each of the circuit breakers, checking that the
breakers do not trip, and that power is delivered
to the proper loads.
If you require an assembled UL Listed panel, Crestron
offers this service through its UL Listed panel shop. This
includes complete in factory system configuration and
assembly by Crestron for an additional fee.
Wiring Diagram of the Terminal Block to the Feed and
Load(s)(Single-wide and Left Side Double-wide Enclosures)
Terminal Block Installation and Field
Wiring
TO
LOAD
4
TO
LOAD
3
TO
LOAD
2
TO
LOAD
1
LINE 1 (*)
LINE 2 (*)
LINE 3 (*)
LINE 4 (*)
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
GROUNDING
TERMINAL
BLOCK
GND
TERMINAL
BLOCK
LEFT
SIDE
WIRING
LABEL
AREA FOR
MODULE
LOCATION
LABEL
BYPASS
JUMPERS
(*) FROM 15 OR 20 AMP
CIRCUIT BREAKER
NOTE: Both left-side and right-side adhesive wiring
labels are provided. The left-side labels are used in both
single and double-wide enclosures. The right-side labels
are only used in double-wide enclosures.
1. Remove the backing from the left or right
adhesive wiring label.
2. Apply the adhesive label by aligning the holes in
the label with the holes on the Crestron
Automation Enclosure where the terminal block
is to be mounted. The wiring label lies beneath
the terminal block as shown in the two wiring
diagrams on this page.
3. Use the two supplied self-tapping pan Phillips
screws (8B x ÂĽ length) to secure the terminal
block to the Crestron Automation Enclosure.
CAUTION: Bypass jumpers are provided to allow
testing of circuits and to protect the module during
installation. When properly secured by two screws,
each of the four jumpers on the black and red
sections of the terminal block shorts the LINE in to
SWITCH out so that the circuit is energized. Do not
remove any bypass jumpers until all feed and load
wiring has been completed, the circuit has been tested
for electrical faults, and the module has been
installed. Refer to “Module Installation” on next
page.
Furthermore, the four jumpers on the white sections
of the terminal block tie the neutral ins to the neutral
outs. These jumpers should never be removed.
Wiring Diagram of the Terminal Block to the Feed and
Load(s) (Right Side Double-wide Enclosures)
TO
LOAD
1
TO
LOAD
2
TO
LOAD
3
TO
LOAD
4
LINE 1 (*)
LINE 2 (*)
LINE 3 (*)
LINE 4 (*)
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
GRO UNDING
TERMINAL
BLOCK
GND
TERMINAL
BLOCK
RIGHT
SIDE
WIRING
LABEL
AREA FOR
MODULE
LOCATION
LABEL
BYPASS
JUMPERS
(*) FROM 15 OR 20 AMP
CIRCUIT BREAKER
NOTE: Use copper conductors only – rated 75°C
4. With the circuit breaker turned off, connect the
circuit feed (LINE and NEUTRAL) and
controlled circuit (LOAD) wires to the terminal
block per the markings provided on the wiring
label (as shown in the diagrams on this page).
Terminal blocks accept one 14 - 10 AWG wire.
Wires should be stripped to ½ inch. Tighten
terminal blocks to 9 in-lbs.
2 •
•
•
•• Terminal Block & Module: CLT- & CLX-4HSW4 Installation Guide – DOC. 5986C
Crestron CLT- & CLX-4HSW4 Terminal Block & Module
Module Installation
CAUTION: Module contains electrostatic sensitive
devices (ESDs); unit must be handled from metal chassis
– do not touch PC board or components.
NOTE: Modules are to be installed after enclosure has
been completely wired. Refer to the terminal block
installation procedure on page 2 for details.
1. Use the four supplied self-tapping pan Phillips
screws (8B x ÂĽ length) to secure the module to
the enclosure.
2. As shown in the wiring diagrams (next column),
connect the wires from the module to the
terminal block. Each wire exits the module
directly in line with, and is the same color as, the
terminal to which it should be connected. Wires
are pre-stripped to ½ inch. Tighten to 9 in-lbs.
3. If the module is being installed above another
module within the enclosure, attach the supplied
module interconnect cable between the two
modules. The illustration below depicts the area
within a double-wide enclosure where the
corners of four modules meet.
NOTE: One wire on the module interconnect cable
may be a different color from the rest. The color has
no bearing on its orientation during installation.
Use Module Interconnect Cable to Wire Module to Module
MODULE
INTERCONNECT
CABLE ATTACHED
CONNECTION
NOT
MADE
4. Turn on the circuit breakers and verify that the
green PWR LED on the module lights, the
breakers do not trip, and power is delivered to
the proper loads.
5. Turn off the circuit breakers and remove the two-
position bypass jumpers on the black and red
sections of the terminal block. The jumpers on
the white sections of the terminal block remain
installed. Refer to the figures in the next column
for a close-up of the jumpers.
NOTE: Before the two-position bypass jumpers,
shown in the illustration, are removed, the Crestron
Professional Automation Computer (PAC2 or
PAC2M), which provides control to the system,
should be properly connected and contain a valid
program to provide control of the module.
Wiring Diagram of the Terminal Block to the Module
(Single-wide and Left Side Double-wide Enclosures)
ATTACH MODULE INTERCONNECT
CABLE (DESCRIBED IN STEP 3)
ENLARGEMENT DETAIL:
LOCATION OF TWO-POSITION
JUMPERS ON TERMINAL
BLOCK AS DESCRIBED IN
STEP 5.
JUMPERS ON BLACK AND
RED SECTIONS OF TERMINAL
BLOCK HAVE BEEN
REMOVED AFTER LOOSENING
SCREWS.
JUMPERS ON WHITE
SECTIONS REMAIN INSTALLED.
JUMPERS
R E D
BLACK
W H IT E
R E D
BLACK
W H IT E
R E D
BLACK
W H IT E
R E D
BLACK
W H IT E
W H I T E
W H IT E
W H IT E
W H IT E
Wiring Diagram of the Terminal Block to the Module
(Right Side Double-wide Enclosures)
JUMPERS
ATTACH MODULE INTERCONNECT
CABLE (DESCRIBED IN STEP 3)
ENLARGEMENT DETAIL:
LOCATION OF TWO-POSITION
JUMPERS ON TERMINAL BLOCK
AS DESCRIBED IN STEP 5.
JUMPERS ON WHITE
SECTIONS REMAIN INSTALLED.
JUMPERS ON BLACK AND
RED SECTIONS OF TERMINAL
BLOCK HAVE BEEN
REMOVED AFTER LOOSENING
SCREWS.
R E D
BLACK
W H IT E
R E D
BLACK
W H IT E
R E D
BLACK
W H IT E
R E D
BLACK
W H IT E
W H IT E
W H I T E
W H IT E
W H IT E
6. Turn on the circuit breakers.
Installation Guide – DOC. 5986C Terminal Block & Module: CLT- & CLX-4HSW4 •
•
•
•• 3


Produktspezifikationen

Marke: Crestron
Kategorie: Nicht kategorisiert
Modell: CLX-4HSW4
Breite: 176 mm
Tiefe: 87 mm
Höhe: 193 mm
Menge pro Packung: 1 StĂĽck(e)