APC SYA8K16RMP Bedienungsanleitung
APC
Unterbrechungsfreies Stromversorgungssystem
SYA8K16RMP
Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für APC SYA8K16RMP (2 Seiten) in der Kategorie Unterbrechungsfreies Stromversorgungssystem. Dieser Bedienungsanleitung war für 16 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/2
Symmetra LX
Rack-mount UPS
Symmetra LX
Tower UPS
®
®
990-1539B-001, 04/2006
Important Safety and Installation Instructions
This manual provides instructions on the wiring and connections for the
Symmetra LX tower and rack-mount UPS.
All electrical power and power control wiring must be installed by a qualified
electrician and comply with local and national regulations.
See and retain the product documentation shipped with your system for
other important installation, operation, and maintenance instructions.
Illustrations are representative. Your Symmetra LX configuration, including
components and optional APC equipment, may be different from the models
shown in this guide.
Entire contents copyright 2006 by American Power Conversion Corporation.
All rights reserved. Reproduction in whole or in part without permission is
prohibited.
Symmetra LX
Electrical Installation Guide
Tower and Rack-mount UPS
®
For use with Symmetra LX UPS Models:
APC, the APC logo, PowerChute, InfraStruXure, Smart-UPS and Symmetra
are registered trademarks of American Power Conversion Corporation. All
other trademarks are the property of their respective owners.
200 V, 4 8 kV A
208/240 V, 4 8 kV A
200 V, 4 16 kV A
208/240 V, 4-16 kVA
Remove screws and slide out the hardwire assembly .
Attach an input conduit and if required, an output conduit .
Larger holes can be punched if necessary.
Detach the strain relief panel using nuts for easier access.
q
q
Complete Pre-installation Checklist
Check that the circuit breaker to be used to power the UPS is in the
OFF position.
Check that the input circuit breaker on the UPS is in the OFF
position.
Before beginning the electrical installation, perform the following procedures.
1
Read, understand and follow ALL safety instructions contained in
the
Failure to follow safety instructions and warnings could
result in equipment damage, serious injury, or death.
Symmetra LX Safety Instructions and General Information
Guide.
Electrical
Hazard
§
§
§
Refer to local and national codes. Many locations require hardwiring
by a licensed electrician.
Strain relief is required for all hardwiring.
All openings in the hardwire assembly must be covered. Failure to
do so may result in personal injury or equipment damage.
Hardwire the UPS
2
1.1
1.2
Caution
2.1
2.2
Electrical Installation
Maximum
Load
Maximum
Load
8 kVA
Circuit
Breaker
Rating*
Circuit
Breaker
Rating*
50 A
Connection
Connection
§
§
§
§
40 in-lb
4.5 -m)
4-Wire ( )
External circuit breaker
#3 AWG (22 mm JAPAN)
Torque to
( N
L1-L2-N-G
2
§
§
§
§
40 in lb
4.5 -m)
4-Wire (L1-L2-N-G)
External circuit breaker
#6 AWG (14 mm JAPAN)
Torque to -
( N
2
Voltage
(Vac)
Voltage
(Vac)
16 kVA 100 A
200, 208,
or 240
200, 208,
or 240
8 kVA 50 A §
§
§40 in lb
m)
§
External circuit breaker
#6 AWG (14 mm JAPAN)
Torque to -
(4.5 N-
2
4-Wire (L1-L2-N-G)
§
§
2 (L14-30R)
4 (L5-20R)
16 kVA 90 A
100/200,
120/208,
or 120/240
100/200,
120/208,
or 120/240
§
§
§
§
40 in lb
m)
External circuit breaker
#3 AWG (22 mm JAPAN)
Torque to -
(4.5 N-
4-Wire
2
(L1-L2-N-G)
§
§
4 (L14-30R)
8 (L5-20R)
Input Connections
Method
Method
Hardwired
(Standard on
tower and
rack-mount)
Hardwired
(Standard on
tower and
rack-mount)
Hardwired
(Standard on
tower and
rack-mount)
Hardwired
(Standard on
tower and
rack-mount)
Output
receptacles
(Standard on
rack-mount)
Output
receptacles
(Standard on
rack-mount)
100/200,
120/208,
or 120/240
100/200,
120/208,
or 120/240
Output Connections
*Recommended
L2
OUTPUT
N
INPUT
L1NL2L1
885-1821/1
24
Vdc
Attach an input cable and an output cable (if required) , to
the terminal block .
Pull the wires through the conduit into the hardwire assembly.
40 in lb
Reinstall the hardwire assembly with provided screws .
Test the wiring.
Turn on the utility power, the input circuit breaker , and the
system enable switch . If the Vin value on the display does
not match your branch voltage, check the input wiring.
Check the output wiring by turning on the maintenance bypass
switch .
§
§
§
§
§
Connect to the terminal block as indicated on the label ,
using a torque of - (4.5 N-m).
Cover the unused holes in the strain relief panel.
Inspect cable connections to ensure proper installation.
Reattach the strain relief panel with nuts .
Turn OFF the input circuit breaker and maintenance bypass
switch.
3
2
If your configuration includes an additional management accessory
card, install in the empty slot on the rear of the UPS. See the
accompanying documentation for installation instructions.
Loads can be connected directly to the UPS using the output
receptacles on the PDU panel. Ensure that the total load being
plugged into a PDU panel DOES NOT EXCEED the branch circuit
breaker rating on the PDU panel.
Install PDU Panel(s) and Connect Loads to the UPS,
If Applicable
5
Your configuration may include optional PDU panels. Refer to the PDU
installation guide.
Note
!
!
!
!!
Remove the access panel to connect the circuits .
If your installation will use an external switch contact, connect
the REPO switch with the pre-installed jumper , as shown.
If your installation will use a switch contact and a 24 V power supply
external to the UPS, remove the jumper and connect the REPO
switch, as shown.
§
§
In many locations, the Remote Emergency Power Off
(REPO) switch must be installed by a licensed electrician.
Refer to local and national codes.
See the
for REPO requirements and detailed safety instructions.
Safety and General Information GuideSymmetra LX
Note
!
!
!
!!
Connect Remote Emergency Power Off (REPO)
Circuit, If Required
Hardwire the UPS (continued)
Install Accessory Card, If Applicable
4
3.1
3.2
3.3
2.3
2.4
2.5
2.6
2.7
2.8
L2
OU T PUT
N
INPUT
L1NL2L1
885-1821/1
Produktspezifikationen
Marke: | APC |
Kategorie: | Unterbrechungsfreies Stromversorgungssystem |
Modell: | SYA8K16RMP |
Akustische Signale: | Ja |
Gewicht: | 198640 g |
Akkuladezeit: | 3 h |
Akku-/Batterietechnologie: | Plombierte Bleisäure (VRLA) |
Betriebstemperatur: | 0 - 40 °C |
Zertifizierung: | CSA,FCC Part 15 Class A,UL 1778 |
Temperaturbereich bei Lagerung: | -15 - 45 °C |
Geräuschpegel: | 62 dB |
Schnittstelle: | DB-9 RS-232, Smart-Slot |
Abmessungen (BxTxH): | 472 x 688 x 836 mm |
Ausgangsleistung: | 6400 W |
Eingangsfrequenz: | 50/60 Hz |
Ausgangskapazität: | 8 kVA |
Typische Backup-Zeit bei halber Belastung: | 17 min |
Typische Backup-Zeit bei voller Belastung: | 5.9 min |
Nominale Eingang Spannung: | 208 V |
Ausgang Anschlüsse: | 1x 4-wire\n4x NEMA L14-30R\n8x NEMA L5-20R |
Eingang Verbindungstyp: | 4-wire |
Notstrom Aus (EPO): | Ja |
Ausgang Spannung (Note): | Configurable for 120/208 or 120/240 output voltage |
Brauchst du Hilfe?
Wenn Sie Hilfe mit APC SYA8K16RMP benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem APC
8 Juni 2024
8 Juni 2024
8 Juni 2024
8 Juni 2024
8 Juni 2024
8 Juni 2024
24 Mai 2024
22 Mai 2024
21 Mai 2024
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem
- Unterbrechungsfreies Stromversorgungssystem Approx
- Unterbrechungsfreies Stromversorgungssystem HP
- Unterbrechungsfreies Stromversorgungssystem Voltcraft
- Unterbrechungsfreies Stromversorgungssystem Siemens
- Unterbrechungsfreies Stromversorgungssystem Schneider
- Unterbrechungsfreies Stromversorgungssystem Lenovo
- Unterbrechungsfreies Stromversorgungssystem Tripp Lite
- Unterbrechungsfreies Stromversorgungssystem Adj
- Unterbrechungsfreies Stromversorgungssystem JUNG
- Unterbrechungsfreies Stromversorgungssystem Block
- Unterbrechungsfreies Stromversorgungssystem Digitus
- Unterbrechungsfreies Stromversorgungssystem CyberPower
- Unterbrechungsfreies Stromversorgungssystem Eaton
- Unterbrechungsfreies Stromversorgungssystem EnerGenie
- Unterbrechungsfreies Stromversorgungssystem Furman
- Unterbrechungsfreies Stromversorgungssystem Riello
- Unterbrechungsfreies Stromversorgungssystem Steren
- Unterbrechungsfreies Stromversorgungssystem Puls Dimension
- Unterbrechungsfreies Stromversorgungssystem Atlantis Land
- Unterbrechungsfreies Stromversorgungssystem Phoenix Contact
- Unterbrechungsfreies Stromversorgungssystem Middle Atlantic
- Unterbrechungsfreies Stromversorgungssystem Minuteman
- Unterbrechungsfreies Stromversorgungssystem Salicru
- Unterbrechungsfreies Stromversorgungssystem Maruson
- Unterbrechungsfreies Stromversorgungssystem Minute Man
- Unterbrechungsfreies Stromversorgungssystem DEXP
- Unterbrechungsfreies Stromversorgungssystem Bxterra
- Unterbrechungsfreies Stromversorgungssystem Altronix
- Unterbrechungsfreies Stromversorgungssystem FSP
- Unterbrechungsfreies Stromversorgungssystem PowerWalker
- Unterbrechungsfreies Stromversorgungssystem FSP/Fortron
Neueste Bedienungsanleitung für -Kategorien-
22 Juni 2024
22 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024