APC MGE Galaxy 3500 Bedienungsanleitung

APC UPS MGE Galaxy 3500

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für APC MGE Galaxy 3500 (12 Seiten) in der Kategorie UPS. Dieser Bedienungsanleitung war für 4 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/12
990-1957A-001 4/2009
*990-1957A-
Installation
MGEâ„¢ Galaxyâ„¢ 3500
10-30 kVA 208/220 V with batteries
IMPORTANT SAFETY INSTRUCTIONS
- SAVE THESE INSTRUCTIONS
Warning: ALL safety instructions in the Safety Sheet
(990-2940) must be read, understood and followed when
installing the UPS system. Failure to do so could result in
equipment damage, serious injury, or death.
Warning: After the UPS has been electrically wired, do
not start it up. Start-up is commissioned to authorized
personnel from Schneider Electric.
Caution: All electrical power and power control wiring
must be installed by a qualified electrician, and must comply
with local and national regulations for maximum power
rating.
Note: Ensure that the unit is in its final location prior to
installation.
Note: Battery and utility power must not be connected until
all other wiring has been completed.
See Also: For parallel configurations see manual 990-
3568.
Level the Enclosure
Warning: The system must be installed on a level floor.
The leveling feet will stabilize the enclosure, but will not
account for a badly sloped floor.
 Use a 13/14 mm wrench to adjust the four leveling feet.
 Ensure that the system is level.
Caution: Do not move the enclosure after the leveling feet
have been lowered.
Floor Anchoring (if applicable)
Anchor the UPS enclosure to the floor
Note: Floor-anchoring bolts are not provided with the UPS.
Purchase the bolts locally (minimum size: M8). Follow the
specifications given by the manufacturer of the floor
anchoring system when bolting the UPS system to the floor.
 Reuse the two transport brackets (one
on each side) that were used to secure the
UPS to the pallet during transport.
 Drill two to six holes in the floor for
each bracket. Attach with bolts.
Prepare for Cables
Bottom cable entry
 From the rear of the UPS, loosen the six
M4 screws from the upper cover (the cable
landing area), and remove. Save the screws
for later use.
 Loosen the two M4 screws (one on each
side) from the top part of the conduit box.
Loosen the M4 screws attaching it to the
bottom part (two screws in a 352 mm (13.8
in) enclosure), (three screws in a 523 mm
(20.50 in) enclosure) and remove. Save the
screws for later use.
 Loosen the four M4 screws (two on each
side) from the conduit box bottom and
remove. Save the screws for later use.
 Punch as many holes as
needed in the marked areas
of the bottom conduit box.
 Attach the conduit box
bottom to the enclosure
(reuse the screws from step
.
 Attach conduits to the
conduit box.
 Run the cables through
the conduits, the bottom of
the conduit box, and up into
the cable landing area.
 Attach the conduit box top to the conduit box bottom, and to the
enclosure reusing the screws from step .
 Fasten the cables with cable ties.
UPS
UPS XR battery enclosure









Bypass
Output
Battery
Mains






2
Connect the AC Input and AC
Output Cables
Warning: Use compression type lugs ONLY.
Do not loosen or add cables to any factory preinstalled
cables on busbars. Use upper part of busbar for
connection only.
Single mains
 Connect the AC input cables
and the neutral to the input
cable landings.
 Connect the AC output
cables and the neutral to the
output cable landings.
 Connect the ground cables to
the studs (earth symbol
beneath) using a screw.
Dual mains Connect the DC Battery Cables
(if applicable)
 Connect battery
cables BAT+, BAT–, and
N to the battery cable
landings.
Connect the Communication
Cables
Warning: Make sure that the UPS is completely OFF as
the connectors are very close to the power busbars.
J106 and J108 pin connections
Note: The UPS must be connected to either a dry contact or
a 24 VDC EPO (Emergency Power Off) switch.
Note: The external EPO +24 VDC, 1500 mA circuit can be
supplied through other vendors.
Note: Always follow the pin connection procedures from
the top and work down: J106 (8-1), J108 (1-6).



 Remove the
three busbars A,
B, and C by
removing two M6
screws from each
busbar.
 Connect the AC
input cables and
the neutral to the
input cable
landings.
 Connect the
bypass cables and
the neutral to the
bypass cable
landings.
 Connect the
output cables and
the neutral to the
output cable
landings.
 Connect the
ground cables to
the studs (earth
symbol beneath)
using a screw.


J108 pin connections:
1 Normally open EPO
2 Normally open EPO return
3 Normally closed EPO
4 Normally closed EPO return
5 +24 V SELV supply
6 SELV ground



J106 pin connections:
8 Ext. charging control return
7 External control of charging
6 Q3 active return
5 Q3 active
4 Battery measurement supply*
3 Battery unit quantity*
2 Max. battery temperature*
1 Battery measurement return*
* Should be used with APC XR
Enclosures
