Installation 990-6486-001 3/2021
Easy UPS 3S Dry Contact I/O SmartSlot Card
(E3SOPT010)
NOTE: Only one dry contact I/O SmartSlot card can be installed in the UPS.
Characteristics of output contacts (pin 3, 5 – 9):
• Permissible voltage: 24 V
• Permissible current: 1 A
Definitions of Output Contacts (Pin 3, 5 – 9)
Pin Pin name Description
3 Utility/mains
unavailable
Utility/mains is unavailable.
Active: low
5 UPS on UPS is in normal mode.
Active: low
6 Battery low Battery voltage reaches EOD.
Active: low
7 General alarm UPS gives off general alarm such as input out of
tolerance, battery low, manual bypass, or output
overload.
Active: low
8 Bypass active or No
output
UPS is in bypass mode, or there is no output power to
load.
Active: low
9 UPS inoperable UPS is inoperable in cases of REC inoperable, INV
inoperable or Bypass inoperable.
Active: low
Characteristics of input contact (pin 4):
NOTE: Do not duplicate the settings of the internal configurable dry contactor
(standard in the UPS) on pin 4 to shut down the UPS.
• Permissible voltage: 24 V
• Permissible current: 80 mA
• Reverse max voltage: 6 V
Definitions of Input Contact (Pin 4)
Pin Pin name Description
4 Shut down UPS UPS can be shut down by energizing this pin with
external power supply for at least two seconds.
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com
As standards, specifications, and design
change from time to time, please ask for
confirmation of the information given in this
publication.
© 2021 – 2021 . All rightsSchneider Electric
reserved.
Easy UPS 3S Dry Contact I/O SmartSlot Card (E3SOPT010)
Definitions of Other Contacts (Pin 1, 2)
Pin Pin name Description
1 VCC Power supply common for output contacts. Must
apply external power supply max 24 V to pin 1
and pin 2.
2 GND Common ground for external power supply and
input/output signal.
1. Assemble the dry contact I/O SmartSlot card:
a. Add the black protective film to the front bracket.
b. Install the PCBA board on the front bracket and fasten with the screw
provided. Torque to 0.49 Nm (0.37 lb-ft/4.33 lb-in).
2 990-6486-001
Easy UPS 3S Dry Contact I/O SmartSlot Card (E3SOPT010)
2. Remove the SmartSlot cover from the rear panel of the UPS.
Rear View
3. Insert the dry contact I/O SmartSlot card into the SmartSlot and fix with the
screws. Torque to 0.49 Nm (0.37 lb-ft).
Rear View
990-6486-001 3


Produktspezifikationen

Marke: APC
Kategorie: Unterbrechungsfreies Stromversorgungssystem
Modell: E3SOPT010

Brauchst du Hilfe?

Wenn Sie Hilfe mit APC E3SOPT010 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem APC

Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem

Neueste Bedienungsanleitung für -Kategorien-