APC Back-UPS 400 Bedienungsanleitung

APC UPS Back-UPS 400

Lesen Sie kostenlos die đź“– deutsche Bedienungsanleitung fĂĽr APC Back-UPS 400 (2 Seiten) in der Kategorie UPS. Dieser Bedienungsanleitung war fĂĽr 5 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
Back-UPS ES 400/550/700
User’s Guide
™
1Connect Battery
For safety, the Back-UPS ES is shipped with one battery wire disconnected. The Back-UPS ES will not operate until the wire is connected to the touch
safe battery terminal.
NOTE: Small sparks may occur during battery connection. This is normal.
TURN the Back-UPS ES over and
slide the battery compartment
cover off of the battery housing.
1 2 3
LIFT the battery out of the compartment
and connect the black wire to the
negative (-) battery terminal. Ensure the
batteries are installed as shown below.
Slide the battery compartment cover
back onto the battery housing.
Place the Back-UPS ES to avoid:
- Direct sunlight
- Excessive heat
- Excessive humidity or contact with fluids
Plug the Back-UPS ES power cord directly into a wall outlet; not a
surge protector or power strip. The wall outlet should be located near
the equipment and be easily accessible.
Connect Modem / Phone / DSL / Fax / 10/100 Base- T/HPNA to
Surge Protection.
The Back-UPS protects a single line (2-wire) phone (including Digital
Subscriber line - DSL), Home Phoneline Networking Association (HPNA)
type equipment, modem, 10/100 Base-T Ethernet, or fax machines from
surges when connected through the UPS as shown in the drawing below.
Note: Telephone Cable OR Network Cable should be connected to Surge
Protection ports. Do not connect the UPS surge protection ports to both
Telephone and Network System cables at the same time.
Connect Computer Cable (This is applicable for 550/700 only)
The supplied cable and software provide automatic file saving and
shutdown of the operating system in the case of a sustained power outage.
Connect the cable to the Data Port of the Back-UPS ES. Connect the other
end of the cable to the USB port on your computer. The software will
automatically find the USB Port of your computer.
2Connect Equipment
Surge Protection Only
These outlets provide full-time protection from surges even if
the Back-UPS ES is switched OFF. Plug your printer, fax
machine, scanner, or other peripherals that do not need
battery power into these outlets.
Battery Backup Surge Protection
These outlets are powered whenever the Back-UPS ES is
switched ON. During a power outage or other AC
problems (brownouts, over-voltages), these outlets will be
powered for a limited time by the Back-UPS ES. Plug your
computer, monitor, and two other data-sensitive devices
(external disk or tape drive) into these outlets.
3Power On and
Install Software
EN 990-2375A
Press the ON/OFF switch to power the unit
ON.
A single short beep and the green “Power On”
indicator confirms that Back-UPS ES is on and
ready to provide protection.
The Back-UPS ES should charge for at least
16 hours to ensure sufficient runtime. The unit
is being charged whenever it is connected to
AC power, whether the unit is turned ON or
OFF.
Install the PowerChute™ Personal
Edition software (This is applicable for
550/700 only.)
Place the PowerChute Personal Edition CD-
ROM into your computer and follow the
installation instructions on the screen.
Status Indicators
The Back-UPS ES indicates operating status using a combination of visual and audible indicators.
Use the following table to identify the status of the Back-UPS ES.
Status Visual Indications
(Power On - Green)
(Replace Battery - Red)
Audible Indication Alarm Terminates
When
Power On - UPS is supplying conditioned
AC power to the load. Power On LED - ON None Not applicable.
On Battery - UPS is supplying battery
power to the load connected to the Battery
outlets.
Power On LED - ON (off
during beep) Beeping 4 times every
30 seconds UPS transfers back to
Power On operation, or
when UPS is turned off.
Low Battery Warning - UPS is supplying
battery power to the load connected to the
Battery outlets and the battery is near
exhaustion.
Power On LED - flashing Rapid beeping (every
1/2 second) UPS transfers back to
normal operation, or
when UPS is turned off.
Replace Battery - Battery is in need of
charging or is at the end of its usual life and
must be replaced.
Power On and Replace
Battery LEDs - Flashing
(alternating)
Constant tone UPS turned off with the
power switch.
Battery Disconnected - The battery is
disconnected or bad battery. Replace Battery LED -
flashing Constant tone UPS turned off with the
power switch.
Overload Shutdown - During On Battery
operation a battery power supplied outlet
overload was detected.
None Constant tone UPS turned off with the
power switch.
Sleep Mode - During On Battery operation
the battery power has been completely
exhausted and the UPS is waiting for AC
power to return to normal.
None Beeping once every 4
seconds. AC power is restored, or
if AC power is not
restored within 32
seconds, or the UPS is
turned off.
See the Troubleshooting section for additional assistance.
©
2013 APC by Schneider Electric
. APC, the APC logo, Back-UPS and PowerChute are owned by Schneider Electric Industries S.A.S.,
07/2013
or their affiliated companies. All other trademarks are property of their respective owners.
DATALINE OUTPUT
TO COMPUTER USB
FROM WALL JACK
PORT (BACK-UPS ES 550
AND ES 700 ONLY)
TO DSL MODEM,
PHONE, NETWORK
(10/100 Base-T)
bu366a
CIRCUIT BREAKER
PUSH TO RESET
bu365d
POWER ON/
REPLACE BATTERY
INDICATOR
AC LINE
CORD
Troubleshooting
Use the table below to solve minor Back-UPS ES installation or operation problems. Consult Schneider Electric IT (SEIT) Online
Technical Support or call SEIT Technical Support for assistance with problems that cannot be resolved using the table below:
Problem
Specifications
Warranty
Service
Input Voltage 230 Vrms Nominal
Frequency 50 - 60 Hz (auto sensing)
Brownout Transfer 180 Vrms, typical
Over-voltage Transfer 266 Vrms, typical
Output Voltage On Battery 230 Vac rms +/- 8%
Total Amperage (8 outlets) 10 Amps (including UPS output)
UPS Capacity (4 outlets) 400VA/240W 550VA/330W 700VA/405W
Frequency - On Battery 50/60 Hz +/-1 Hz
Transfer Time 6 ms typical, 10 ms maximum
Protection and Filter AC Surge Protection Full time, 310 joules
Phone/fax/DSL Surge
Protection Single line (2-wire)
Network Surge Protection 10/100Base-T Ethernet
EMI/RFI Filter Full time
AC Input Resettable circuit breaker
Battery Type Sealed, maintenance-free lead acid
Average Life 3 - 5 years depending on the number of discharge
cycles and environmental temperature
Physical Net Weight 5.4kg 6.4kg 6.8kg
Dimensions (H x W x D) 285 x 230 x 86 mm
(11.18” x 9.05” x 3.3 in.)
Operating Temperature 0oC to 40 oC (32 oF to 104 oF)
Storage Temperature -15 oC to 45 oC (5 oF to 113 oF)
Operating Relative Humidity 0 to 95% non-condensing
Operating Elevation 0 to 3000 m (0 to 10,000 ft)
The standard warranty is three (3) years from the date of purchase. Schneider Electric
IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned
unit. Customers who must have the original unit back due to the assignment of asset
tags and set depreciation schedules must declare such a need at first contact with an
SEIT Technical Support representative. SEIT will ship the replacement unit once the
defective unit has been received by the repair department, or cross ship upon the
receipt of a valid credit card number. The customer pays for shipping the unit to SEIT.
SEIT pays ground freight transportation costs to ship the replacement unit to the
customer.
If the unit requires service, do not return it to the dealer. Follow these steps:
1. Review the Troubleshooting section of the manual to eliminate common
problems.
2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support
through the APC by Schneider Electric Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The
model and serial numbers are located on the rear panel of the unit and are
available through the LCD display on select models.
b. Call SEIT Customer Support and a technician will attempt to solve the
problem over the phone. If this is not possible, the technician will issue a
Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC b
Schneider Electric Web site for country specific instructions.
3. Pack the unit in the original packaging whenever possible to avoid damage in
transit. Never use foam beads for packaging. Damage sustained in transit is no
covered under warranty.
4. Always DISCONNECT THE UPS BATTERIES before shipping. The United
States Department of Transportation (DOT), and the International Air
Transport Association (IATA) regulations require that UPS batteries be
disconnected before shipping. The internal batteries may remain in the UPS.
5. Write the RMA# provided by Customer Support on the outside of the package.
6. Return the unit by insured, pre-paid carrier to the address provided by Custome
Support.
Order Replacement Battery
Replace with an APC by Schneider Electric qualified battery. Replacement batteries
can be ordered from www.apc.com (valid credit card required). For Back-UPS ES 400,
order APCRBC106 as directed by SEIT Technical Support. For Back-UPS ES 550,
order RBC2. For Back-UPS ES 700, order RBC17.
Item Specification BE400 BE550 BE700
165 mm
(6.50 in.)
Wall Mounting Template
Wall Mount of UPS
APC by Schneider Electric IT
Customer Support Worldwide
For country specific customer support, go to the APC by Schneider Electric Web site,
www.apc.com.
Solution
Back-UPS ES will not turn on.
No power available at the Surge Protection
Only outlets.
Connected equipment loses power.
The Power On indicator is lit and the Back-
UPS ES is beeping four times every 30
seconds.
The Power On indicator flashes once per
second and the Back-UPS ES beeps once per
second at the same time.
Inadequate runtime.
Connect the battery (see Connect Battery) and ensure power is available at the wall
outlet.
Reduce the amount of equipment plugged into Surge Protection Only outlets.
Ensure the fuse or circuit breaker for the outlet is not tripped, and that the wall switch
controlling the outlet (if any) is in the ON position.
Ensure the equipment you want to stay powered during a power failure is plugged
into the Battery Backup/Surge Protection outlets and NOT the Surge Protection Only
outlets.
Make sure the equipment plugged into the Battery Backup/Surge Protection outlets
of the unit are not overloading the capacity of the unit. Try removing some of the
equipment and see if the problem continues.
The Back-UPS ES is operating normally.
The Back-UPS ES can only operate on battery power for a limited amount of time.
The unit will eventually turn off when the available battery power has been used.
Allow the unit to recharge for 16 hours before continuing use of the unit.
The output waveform is designed for computers and computer-related equipment. It
is not designed for use with motor-type equipment.
Contact SEIT Technical Support for further troubleshooting.
The Back-UPS ES is operating normally and using battery power. Once On Battery,
you should save your current work, power down your equipment, and turn the unit
OFF. Once normal power is restored, you may turn the unit back ON and power your
equipment.
The Back-UPS ES is about to shut off due to a low battery charge condition! When
the unit beeps once every second, the battery has about 2 minutes of power
remaining. Immediately power down your computer and turn the unit OFF. When
normal power returns, the unit will recharge the battery.
Allow the unit to charge by leaving it plugged into the wall for at least 16 hours.
As a battery ages, the amount of runtime available will decrease. You can replace
the battery by ordering one at www.apc.com. Batteries also age prematurely if the
Back-UPS ES is placed near excessive heat.
The UPS can be mounted vertically or horizontally to a wall surface. Use the template below to
position the mounting fasteners (not supplied). Wall mount the UPS as follows;
1. Hold this page against the wall in the desired mounting location.
2. Use thumbtacks or tape to hold this page in place against the wall. Use a sharp nail or pin to
puncture the center of each template circle to mark the wall.
3. Install the mounting fasteners at the marked locations. Leave the head of both fasteners 8
mm (5/16) out from the face of the wall. The fasteners must be able to support 6.8 Kg.
4. Mount the UPS by positioning the key-hole slots over the mounting fasteners heads. For ver-
tical mounting, slide the UPS down into place. For horizontal mounting, turn it slightly counter-
clockwise until it is securly in place.
Battery is disconnected or AC power is not available at the
wall outlet.
Surge Protection Only outlets have been overloaded.
AC power not available at the wall outlet.
Equipment is connected to the Surge Protection Only
outlets.
The Back-UPS ES is overloaded.
PowerChute Personal Edition software has performed a
shutdown due to a power failure.
The Back-UPS ES has exhausted its available battery
power.
Connected equipment does not accept the step-
approximated sine waveform of the Back-UPS ES.
The Back-UPS ES may require service.
The Back-UPS ES is using battery.
Battery capacity is low (about 2 minutes of use remaining).
The battery is not fully charged.
Battery is near the end of useful life.


Produktspezifikationen

Marke: APC
Kategorie: UPS
Modell: Back-UPS 400

Brauchst du Hilfe?

Wenn Sie Hilfe mit APC Back-UPS 400 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung UPS APC

Bedienungsanleitung UPS

Neueste Bedienungsanleitung fĂĽr -Kategorien-