Air King DL4S Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Air King DL4S (12 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 3 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/12
www.airkinglimited.com6727902 Rev. H 7/22 1 of 12
SAVE THESE INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer.
b) Before servicing or cleaning the unit, switch power off at service panel
and lock the service disconnecting means to prevent power from being
switched on accidentally. When the service disconnecting means
cannot be locked, securely fasten a prominent warning device, such as
a tag, to the service panel.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK AND INJURY TO PERSON,
OBSERVE THE FOLLOWING:
a) Installation work and electrical wiring must be done by qualified person(s)
in accordance with all applicable codes and standards, including fire-
related construction.
b) Sufficient air is needed for proper combustion and exhausting of gases
through the flue (chimney) of fuel burning equipment to prevent back
drafting. Follow the heating equipment manufacturer’s guideline and
safety standards such as those published by the National Fire Protection
Association (NFPA) and the American Society for Heating, Refrigeration,
and Air Conditioning Engineers (ASHRAE), and the local code authorities.
c) When cutting or drilling into wall or ceiling, do not damage electrical wiring
and other hidden utilities.
CAUTION: FOR GENERAL VENTILATING USE ONLY.
DO NOT USE TO EXHAUST HAZARDOUS OR EXPLOSIVE
MATERIALS AND VAPORS.
d) Ducted fans must always be vented to the outdoors.
e) If this unit is to be installed over a tub or shower, it must be marked as
appropriate for the application and be connected to a GFCI (Ground Fault
Circuit Interrupter) – protected branch circuit.
f) Do not install in a ceiling with thermal insulation value greater than R40.
g) This unit must be grounded.
h) To avoid motor bearing damage and noisy and/or unbalanced impellers,
keep drywall spray, construction dust, etc. off power unit.
i) Read all instructions before installing or using exhaust fan.
WARNING: TO REDUCE THE RISK OF FIRE,
ELECTRIC SHOCK, DO NOT USE THIS FAN WITH ANY
SOLID-STATE SPEED CONTROL DEVICE.
WARNING: DO NOT USE IN KITCHENS.
WARNING: THE DUCTING FROM THIS FAN TO THE
OUTSIDE OF THE BUILDING HAS A STRONG EFFECT ON THE AIR
FLOW, NOISE AND ENERGY USE OF THE FAN. USE THE SHORTEST,
STRAIGHTEST DUCT ROUTING POSSIBLE FOR BEST PERFORMANCE, AND
AVOID INSTALLING THE FAN WITH SMALLER DUCTS THAN RECOMMENDED.
INSULATION AROUND THE DUCTS CAN REDUCE ENERGY LOSS AND
INHIBIT MOLD GROWTH. FANS INSTALLED WITH EXISTING DUCTS MAY
NOT ACHIEVE THEIR RATED AIRFLOW.
READ AND SAVE THESE INSTRUCTIONS
READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN
THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY
INFORMATION. FAILURE TO COMPLY WITH INSTRUCTIONS COULD RESULT IN PERSONAL
INJURY AND/OR PROPERTY DAMAGE!
RETAIN INSTRUCTIONS FOR FUTURE REFERENCE.
GENERAL SAFETY INFORMATION
When using electrical appliances, basic precautions should
always be followed to reduce the risk of fire, electric shock and
injury to person, including the following:
Exhaust Fan
D4D, D4DG, D4DH, D4DGH
IMPORTANT INSTRUCTIONS - OPERATING MANUAL
www.airkinglimited.com6727902 Rev. H 7/22 2 of 12
INSTALLATION INSTRUCTIONS
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT SERVICE
PANEL BEFORE STARTING INSTALLATION.
SECTION 1
Preparing the Exhaust Fan
1. Unpack fan from the carton and confirm that all pieces are present. In addition to the
exhaust fan you should have:
1 - Grill
1 - Damper Assembly (attached)
4 - Mounting Rails
1 - Mounting Flange
1 - LED Lamp
1 - Instruction/Safety Sheet
2. Choose the location for your fan. To ensure the best air and sound performance, it is
recommended that the length of ducting and the number of elbows be kept to a minimum,
the radius of each elbow be as large as possible for the installation, and that insulated hard
ducting be used. Larger duct sizes will reduce noise and airflow restrictions. This fan will
require at least 10 of clearance in the ceiling or wall, and will mount through drywall up
to 3/4 thick.
3. No additional vibration deadening materials are needed for this fan.
SECTION 2
New Construction
NOTE: If the mounting flange is installed on the fan housing, remove the two screws that connect
the ceiling mounting flange to the housing and set aside (Figure 12).
1. Install the rails into the mounting channel on the housing. Center the mounting channel in
the slots on the housing, then from inside the housing tighten the mounting channel nuts
so the channel is securely in place. Position the housing next to the joist. Line up housing
so that it will be flush with the finished ceiling. Secure the ends of the rails with screws or
nails (not included) to the joists and slide the housing into the final position (Figure 1).
Figure 1
Housing
Joist
Mounting Rails
SECTION 3
Existing Construction
NOTE: If the mounting flange is installed on the fan housing, remove the two screws that connect
the ceiling mounting flange to the housing and set aside (Figure 12).
1. Set housing in position between the joist and trace an outline onto the ceiling material
(Figure 2). Set housing aside and cut opening, being careful not to cut or damage any
electrical or other hidden utilities. Install the rails into the mounting channel on the
housing. Center the mounting channel in the slots on the housing, then from inside the
housing tighten the mounting channel nuts so the channel is securely in place. Position the
housing in the previously cut hole so that it is flush with the finished ceiling. Secure the
ends of the rails to the joists (Figure 1).
Figure 2
Joist
SECTION 4
Ducting
NOTE: 6" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.
CAUTION: ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL
BUILDING CODES.
NOTE: The ducting from this fan to the outside of the building has a strong effect on the air
flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible for
best performance, and avoid installing the fan with smaller ducts than recommended. Insulation
around the ducts can reduce energy loss and inhibit mold growth. Fans installed with existing
ducts may not achieve their rated air flow.
1. Connect the ducting to the fan’s duct collar Secure in place using tape or screw (Figure 3).
clamp. Always duct the fan to the outside through a wall or roof cap. It is recommended
that low restriction termination fittings be used.
Ducting
Duct
Collar
Figure 3
2. Ensure duct joints and exterior penetrations are sealed with caulk or other similar material to
create an air-tight path to minimize building heat loss or gain and to reduce the potential for
condensation. Place/wrap insulation around duct and/or fan to in order to minimize possible
condensation buildup within the duct, as well as building heat loss or gain (Figure 4).
Figure 4
Insulation*
(place around and
over Fan Housing
Fan Housing
Power Cable*
Seal gaps
around Housing
Round
Duct*
Seal duct
joints with tape
Round
Elbows*
Wall Cap*
Roof Cap*
(with built-in
damper)
Keep duct
runs short
*Purchase separately
or
SECTION 5
Wiring
CAUTION: MAKE SURE POWER IS SWITCHED OFF AT
SERVICE PANEL BEFORE STARTING INSTALLATION.
CAUTION: ALL ELECTRICAL CONNECTIONS MUST BE MADE
IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL
ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL
WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.
NOTE: This unit includes a side access panel for wiring that does not require the removal of the
fan’s blower assembly. If you choose to wire the unit from the inside, you will need to remove the
blower assembly and internal wiring compartment. Both methods are equally effective.
1a. External Wire Compartment: Remove the wire compartment cover screw and place cover
in a secure place (Figure 5).
www.airkinglimited.com6727902 Rev. H 7/22 3 of 12
Figure 5
Screw
Wire
Compartment
Cover
1b. Internal Wire Compartment: If the motor is already installed in the housing, remove
the two screws holding the blower assembly in place. Lift up on the assembly and slide it
out of the tabs on the housing . Remove the wire compartment cover screw and (Figure 6)
place the cover in a secure place (Figure 7).
Figure 6
Tabs
Screws
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
O
F
F
(x10)
NOTE: If the fan motor plug is connected to the fan housing receptacle, unplug so the blower
assembly can be completely removed.
Figure 7
Screw
Wire Compartment Cover
NOTE: Wire compartment configuration
will be dependent on model.
Standard and Motion Sensing Models
2. Connect the White wire of the fan to the White (Neutral) wire from the power source. Connect
the Black wire of the fan to the Black (Hot) wire from the power source. Connect the ground
wire from the house to the green wire from the fan housing. Using a properly grounded three
function switch (not included) connect the Black wire from the supply to the switch. Connect
the Yellow wire (fan) from the fan housing to one of the terminals on the switch. Connect the
Red wire (light) from the fan housing to a separate terminal on the switch (Figure 8). Use
approved methods for all connections.
Figure 8 Supply from house
Yellow
Neutral (White)
Ground (Green or Bare)
Fan
Neutral (White)
Green
Switch
(by others)
Black
Red
Black
By others
NOTE: There may be more than one white wire to be connected present.
NOTE: The fan’s receptacle wires might need to be pulled outside compartment for connection.
Only pull the five loose wires outside of compartment. Additional wires will be present.
NOTE: Unit must be grounded according to all local and national codes.
Humidity Sensing Models
3a. For proper operation the humidity sensing fan will require a 3 way switch (not included).
Run wiring between the fan and the switch location. Make sure you leave enough wiring
in each box to make the connections. At the switch box connect the black wire from the
house to the common terminal of the switch. Connect the black wire from the fan to one of
the switched terminals on the switch. This position will energize the automatic mode and
the fan will energize upon a rise in humidity. Connect the yellow wire from the fan to the
other switched terminal on the switch. This position will activate the Manual On feature
and energize the fan. Properly connect the ground and neutral (if applicable) mount the
switch and the cover.
The yellow wire may contain a wire crimp nut which will have to be cut off and the NOTE:
wire stripped.
3b. Wiring the Fan: From where you have chosen to access the fan’s junction box, connect
the white wire from the house to the white wire from the fan. Connect the wire from the
automatic position on the wall switch to the black wire from the fan, connect the wire from
the manual On position on the switch to the yellow wire from the fan. Connect the ground
wire from the house to the green wire from the fan housing Use approved (Figure 10).
methods for all connections.
The yellow wire may contain a wire crimp nut which will have to be cut off and the NOTE:
wire stripped.
3c. Wiring the Lights: Using a properly grounded standard wall switch, connect the black
wire from the supply to one side of the switch. Connect the Red wire (light) from the
fan housing to the other terminal on the switch Use approved methods for (Figure 9).
all connections.
Figure 9 Supply from house
Black
Neutral (White)
Ground (Green or Bare)
Fan
Black
Neutral (White)
Green
Switch
(by others)
Black
Red
Switch
(by others)
Yellow
By others
4. Carefully tuck wire back inside wire compartment and replace wire compartment cover
securing with the screw that was removed earlier.
NOTE: The fan’s receptacle wires might need to be pulled outside compartment for connection.
Only pull the five loose wires outside of compartment. Additional wires will be present.
NOTE: Unit must be grounded according to all local and national codes.
SECTION 6
Completing the Installation
1. Use a sealant appropriate for contact with the building materials present and for the
temperature requirements of the installation to prevent air leakage from unconditioned
spaces is recommended. If gaps between unit housing and ceiling are great, additional
material (backing rod, ceiling material) may be required.
NOTE: This fan is rated for direct insulation contact (Type IC) and it is recommended that this fan
be completely covered by insulation in order to reduce heat loss or gain to unconditioned space.


Produktspezifikationen

Marke: Air King
Kategorie: Nicht kategorisiert
Modell: DL4S

Brauchst du Hilfe?

Wenn Sie Hilfe mit Air King DL4S benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Air King

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-