LEF Series
OPEN VOICE SELECTIVE CALL INTERCOM
INSTALLATION & OPERATION MANUAL
LEF-3 (3-call master)
LEF-5 (5-call master)
LEF-10 (10-call master)
LEF-10S (10-call master w/all call button)
Models:
* LEF-5W, LEF-10W & LEF-10SW:
w/Terminal Box prewired
(Not available in North America)
PRECAUTIONS
WARNING (Negligence could result in death or serious injury.)
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Do not dismantle or alter the unit. Fire or electric shock could result.
Keep the unit away from water or any other liquid. Fire or electric shock could result.
For power supply, use Aiphone power supply model specified for use with system. If non-specified product is used, fire or malfunction
could result.
Do not connect any non-specified power source to the +, - terminals. Also, do not install two power supplies in parallel to a single input.
Fire or damage to the unit could result.
Do not use power supply with a voltage other than specified. Fire or electric shock could result.
Keep AC cord from being marred or crushed. If the AC cord is damaged, fire or electric shock could result.
Do not plug or unplug unit with wet hands. Electric shock could result.
Insert AC plug completely and securely into AC outlet. Otherwise, fire or electric shock could result.
Periodically check for and remove dust on the power plug. If dust is left, it could cause the power plug to heat up, resulting in fire.
Do not put any metal or flammable material into the unit through the openings. Fire, electric shock, or unit trouble could result.
1.
2.
3.
4.
5.
6.
7.
CAUTION (Negligence could result in injury to people or damage to property.)
Do not install or make any wire terminations while power supply is plugged in. It can cause electrical shock or damage to the unit.
When mounting the unit on a wall, install the unit in a convenient location, but not where it could be jarred or bumped. Injury could result.
Before turning on power, make sure wires are not crossed or shorted. If not, fire or electric shock could result.
Do not place or install the unit in the locations subject to frequent vibration or impact. If the unit falls, injury to people or damage to the
unit could result.
Do not put anything on the unit or cover the unit with cloth, etc. Fire or unit trouble could result.
Do not install the unit in any of the following locations. Fire, electric shock, or unit trouble could result.
* Places under direct sunlight (except door station).
* Near heating equipment that varies in temperature.
* Places subject to dust, oil, chemicals, hydrogen sulfide (hot spring).
* Places subject to moisture and humidity extremes, such as bathrooms, cellars, greenhouses, etc.
* Places where the temperature is quite low, such as inside a refrigerated area or in front of an air conditioner.
* Places subject to steam or smoke (near heating or cooking surfaces).
* Where noise generating devices such as dimmer switches or inverter electrical appliances are closeby.
* Locations subject to frequent vibration or impact.
* Locations subject to extremely powerful electric fields.
The unit must be installed and wired by a qualified technician.
1.
2.
3.
4.
5.
6.
7.
8.
9.
GENERAL PRECAUTIONS
Keep the unit more than 1m (3.3') away from radio or TV sets.
Keep the intercom wires more than 30cm (12'') away from AC 100-240V wiring. AC induced noise and/or unit malfunction could result.
Comply with all third party manufacturing specifications that will be used with this system.
Using a mobile phone or professional-use radio equipment such as walkie-talkie close to the system may cause a malfunction.
The unit can be damaged if dropped. Handle with care.
The unit will not work during power failure.
In areas where broadcasting station antennas are closeby, the intercom system may be affected by radio frequency interference.
All the units, except for door stations, are designed for indoor use only. Do not use at outdoor locations.
This product, providing door release, should not be used as a crime prevention device.
Prohibited Do not dismantle unit Keep unit away from water General precautions
– 2 –
2 NAMES & FEATURES
LEF-3
LEF-5, 10, 10S
1 Speaker
2 Call-in LED (3)
3 Station-Select button (3)
4 Voice volume control
5 OFF button (w/ON LED)
6 Microphone (initiator only)
7 In-use LED (occupied)
8 Privacy button & LED indicator
9 Talk (listen) button
1 Speaker
2 Call-in LED (5 or 10)
3 Station-Select button (5 or 10)
4 Voice volume control
5 In-use LED (occupied)
6 All Call transmit button & LED ( only)LEF-10S
7 Door release button
8 Microphone (initiator only)
9 OFF button (w/ON LED)
10 Privacy button & LED indicator
11 Talk (listen) button
LEF-5: 5 station buttons and OFF.
Names & functions
Components available
Intercoms: Masters or subs, intermixable
Master stations Sub stations Power supply
LEF-3
3-call
LEF-5
5-call
LEF-10
10-call
LEF-10S
10-call
w/all call button
LE-D
Surface mt.
LE-DA
Flush mt.
LE-A
LE-AN
1-call(w/Priv.)
PS-1225UL
PS-1225S
PS-1225
12V DC, 2.5A power supply
PS-1215DIN, 12V DC, 1.5A
Additional Sub stations:
LE-DL: Surface-mount w/anodized aluminum panel
AH-108 8 horn speaker w/ matching Ω LT-1
transformer & NP-25V (33 fd,bp,25V)μ
All Call & Background Music (with LEF-10S):
BG-10C: All call, chime & music adaptor.
1 SYSTEM OUTLINE & COMPONENTS
System outline
The LEF is a flexible Open Voice Selective Call Intercom system which integrates any combination of master and
sub stations. The system features selective calling from any master with handsfree reply, call-in and LED from a
variety of sub stations, selective door release (except LEF-3), and a variety of other optional features.
LEF intercom (LEF-3, 5,10 or 10S) • Packet of screws
Installation & Operation Manual
• China RoHS paper
Package contents
1
6
7
8
9
2
3
4 5
1 2 3
OFF
OCCUPIED
PRIV TALK
CALL
1 2 3 4 5 6 7 8 9 10
OFF
OCUPIEDVOICE VOL PRIVALL CALL TALK
CALL
1
2
3
4 5 6 7 10 11
8
9
– 3 –
Features
Four LEF master stations, intermixable.
Capacity Door release
All Call transmit
4 stations
6 stations X
11 stations X
Models
LEF-3
LEF-5
LEF-10
LEF-10S 11 stations X X
Optional features:
* All Call, chime & Music distribution (w/ adaptor, LEF-10S only)BG-10C
* Selective door release (w/ relay, 1 per door, excluding LEF-3)RY-PA
* 8 Ω horn speaker ( w/ transformer & capacitor)AH-108 LT-1 NP-25V
* External signaling when door/sub calls (w/ and external device)RY-AC/A
WIRING:
Loop-wired system with multi-conductor shielded cable.
All-master system: 4 common wires + 1 wire per number of stations in the system.
If All Call is included: Add 4 additional common wires ( P1 ~ P3 , Y ).
If Door Release is included (LEF-5/10/10S): Add 1 common L + 1 individual wire
for each door to be released ( K# terminals).
Single-master system: 2 wires homerun* from each sub to the master.
Leave jumpers between E & – installed.
*NOTE: It is recommended even in a single master system that 3 wires are used for
all sub stations in the system, and that the E & jumpers are removed. This ensures
that the wiring is proper in the event of system expansion in the future.
Intermixed system with masters and subs: 3 wires from each sub to the nearest
master, or 2 common + 1 individual wire per station on a loop. Remove jumpers
between E & from all stations in a multi-master system.
Model # # of Conductors Wire # (22AWG) Wire # (18AWG) # of Conductors Wire # (22AWG)
LEF-1C 12 822212 x x x
LEF-3C 12 822212 x x x
LEF-5C 15 822215 x 20 822220
LEF-10C 20 822220 x 30 822220 + 822210
LEF-3 9 822210 x x x
LEF-5 12 822212 x 20 822220
LEF-10 20 822220 x 30 822220 + 822210
LEF-10S 20 822220 x 30 822220 + 822210
LE-A 3 822203 821803 x x
LE-B 3 822203 821803 x x
LE-D 3 822203 821803 x x
LE-DA 3 822203 821803 x x
With selective door release and/or camera
call-up (incl. K wires b/n masters, max.)
Standard Communication (Max. # of stations)
Wire Reference Chart
Speaker
CALL
LE-D
LE-DA
Speaker
CALL
LE-DA
Speaker
CALL
LE-A, 1-call
LE-AN, w/ PRIVACY
Speaker
CALL
PRIV.


Produktspezifikationen

Marke: Aiphone
Kategorie: Türsprechanlage
Modell: LEF-10S
Breite: 190.5 mm
Tiefe: 55.5 mm
Produktfarbe: Black, Grey, White
Höhe: 206.3 mm
Material: Acrylnitril-Butadien-Styrol (ABS)
Befestigungstyp: Tisch/Wand
Energieverbrauch: 300 mA
Markenkompatibilität: Aiphone

Brauchst du Hilfe?

Wenn Sie Hilfe mit Aiphone LEF-10S benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Türsprechanlage Aiphone

Bedienungsanleitung Türsprechanlage

Neueste Bedienungsanleitung für -Kategorien-