Sonel MPI-535 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Sonel MPI-535 (3 Seiten) in der Kategorie Messgeräte. Dieser Bedienungsanleitung war für 7 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/3
ZL-N L-N fault loop impedance
ZL-PE L-PE fault loop impedance
ZL-PE[RCD] L-PE fault loop impedance with RCD
RISO Insulation resistance
RCD IA RCD tripping current
RCD tA RCD tripping time
RCDAUTO Automatic RCD measurements
RX Resistance measurement
RCONT
Resistance measurement with I=±200 mA
1-2-3 Phase sequence
U-V-W Motor rotation direction
RE Resistance-to-earth
Ωm Soil resistivity
ΔU Voltage drop
Lux Illuminance
Touchscreen
Function icons
Back
Save
Show last measurement
Return to main menu
Select item
Show more icons
Add item
Edit item
Search
Remove item
Close menu
Sonel MPI-535
Meter for Electrical Installation Parameters
v1.00 | 11.01.2021
First steps
Turn on the meter Measure Save to the memory
Auto measurements
Proceeding auto measurements Creating measurement procedures
Connect the meter to the measured circuit.
Select an
appropriate
folder and
measurement
sequence from
the list.
Select
to go to the
sequence
wizard.
After each
selection, the
menu with step
parameters will
be shown.
The procedure
will be available
from the main
menu of au-
to-procedures. To
remove it, select
it with and
choose .
In each setting
îš¿eld, enter
the type of
measuring
accessory,
installation pa-
rameters and
other required
data.
Select
to add the
desired
measurement
procedure.
Changing
the order of
the steps is
performed by
using .
Delete the step
by using
icon.
Save the procedure by using icon. A window will be shown
re-questing the name of the procedure.
In the end,
a screen with
a summary of
the measure-
ments will be
displayed.
From the available items select the one, which is to be a part
of the procedure. In addition to standard measurements, the
following are also available:
â–ª text message,
â–ª visual test.
Press START to run the measurements. Follow the
on-screen instructions.
Find more information
in the user manual
and on our website
www. .pl/ensonel
Main
result
Connect the meter to the measured object.
The measurement will start automatically.
Resistance measurement
Finish the measurement and select .
Go to location you want to save the result in.
Save the result with icon .
Saving a result to the memory
Main
result
Evalu-
ation of
the result
Additional
results
Connect the meter to the measured object.
To run new measurement press START.
The measurement will start automatically.
Enter settings
â–ª limit to evaluate the result
R measurement with I=±200 mA
Connect the meter to the measured soil.
Enter settings
â–ª measuring voltage
â–ª L distance between electrodes
â–ª resistivity limit to evaluate the result
Run the measurement with START button.
Main
result
Evalu-
ation of
the result
Additional
results
Connect the meter to the measured circuit.
ZL-L / ZL-N
ZL-PE
ZL-PE
Enter settings
â–ª test leads length L
â–ª basis of calculating Ik current
â–ª type and rated current of the circuit breaker
Run the measurement with START button.
Main
result
Evalu-
ation of
the result
Additional
results
Connect the meter to the measured circuit and choose
the measurement mode. Connect the
meter to the
measured
circuit.
RCD IA
RCD tA
Enter settings
â–ª residual operating current I
Δn
â–ª forced current
â–ª waveform of the measuring current
â–ª type of the RCD
â–ª measuring voltage UL
Enter settings - measurement mode (full / standard) and:
â–ª residual operating current I
Δn
â–ª a multiplicity of RCD rated current
â–ª RCD type / waveform of the measuring current
â–ª type of the RCD
â–ª measuring voltage UL
Run the measurement with START button.
Run the measurement with START button. Tested RCD
switch must be turned on after each triggering, until
measurements are completed.
Main
result
Evalu-
ation of
the result
Additional
results
Soil resistivity
Fault loop impedance RCD test Auto measurements of RCDs
â–ª Connect the meter to the reference point of the tested network,
as for ZL-N measurement.
â–ª Press START.
â–ª Use setting Zref= --- to reset previous measurement, if it has
not been done yet.
▪ Enter the limit of voltage drop ΔUMAX.
â–ª Enter the fuse type, which protects the tested circuit.
â–ª Change the setting from Zref to .Z
â–ª Connect the meter to the reference point, as for ZL-N measurement.
â–ª Press START.
Voltage drop
Eventually,
measured
parameters
are displayed.
The list of
results may be
scrolled on the
screen.
Choose the measurement method.
Enter settings
â–ª measuring voltage
â–ª measurement method
â–ª resistance limit to evaluate the result
Run the measurement with START button.
Main
result
Evalu-
ation of
the result
Additional
results
Resistance-to-earth
The phase sequence is , i.e. the phase correct
sequence is in direction.clockwise
The phase sequence is , i.e. the phase incorrect
sequence is in direction.anticlockwise
Connect the meter to
the measured object.
The check will start
automatically.
Phase sequence
Arrows on the screen rotating to the
left mean that the motor connected to
a 3-phase network will rotate the shaft
to the left.
Connect the meter to the examined
motor.
Vigorously rotate the motor shaft to
the right.
Motor rotation direction
Arrows on the screen rotating to the
right mean that the motor connected
to a 3-phase network will rotate the
shaft .to the right
Choose the measurement method.
Enter settings
â–ª measurement method
â–ª measuring voltage
â–ª duration of the measurement
â–ª resistance limit to evaluate the result
Run the measurement with START button.
Main
result
Evalu-
ation of
the result
Main
result
Evalu-
ation of
the result
Additional
results
Enter settings
â–ª illuminance limit to evaluate the result
Connect measuring probe to the meter.
Main
result
Evalu-
ation of
the result
Additional
results
Insulation resistance Illuminance


Produktspezifikationen

Marke: Sonel
Kategorie: Messgeräte
Modell: MPI-535

Brauchst du Hilfe?

Wenn Sie Hilfe mit Sonel MPI-535 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Messgeräte Sonel

Bedienungsanleitung Messgeräte

Neueste Bedienungsanleitung für -Kategorien-