Mitsubishi PAR-U02MEDA ME Bedienungsanleitung

Mitsubishi Klimaanlage PAR-U02MEDA ME

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Mitsubishi PAR-U02MEDA ME (100 Seiten) in der Kategorie Klimaanlage. Dieser Bedienungsanleitung war für 10 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/100
Simple Panel Design
The compact height (290 mm) and built in drain
lift-up mechanism make this unit ideal for low and
narrow ceiling spaces.
CEILING CASSETTE TYPE | 2-WAY AIRFLOW TYPE
121
SIMPLE PLAN DESIGN
DRAIN PUMP IS EQUIPPED AS
STANDARD FEATURE
SLIM BODY - ONLY 290MM HEIGHT
VANE CONTROL
In-take port is not a grille but made in stylish design. It can be installed in harmony with ceiling and illuminations.
The drain can be positioned anywhere up to 583 mm
from the ceiling's surface, providing greater freedom
with long cross-piping and allowing more versatility with
piping layouts.
The slimline body is highly suited for installation in narrow
ceiling spaces and for replacing obsolete air conditioning
equipment in older buildings. The height of the main unit is
only 290 mm.
Vane angle can be selected from 7 types including
"Horizontal fix" and "Swing" to set an airblow type
according to your taste.
*Airflow direction cannot be changed individually.
Ceiling surface
Drain height
max. 583
Main unit height - 290 (11-7/16)
583
mm
Air blow Swing
Windbreak
Horizontal airflow
290 mm
No
bothersome
cold air.
Air stream
is relaxing.
PLFY-P VLMD-E
2-WAY AIRFLOW TYPE
122
Model PLFY-P20VLMD-E PLFY-P25VLMD-E PLFY-P32VLMD-E PLFY-P40VLMD-E
Power Source 1-Phase 220-240V 50Hz / 1-Phase 220-230V 60Hz
Cooling Capacity*1 kW 2.2 2.8 3.6 4.5
BTU/h 7,500 9,600 12,300 15,400
Heating Capacity*1 kW 2.5 3.2 4.0 5.0
BTU/h 8,500 10,900 13,600 17,100
Power
Consumption
Cooling kW 0.072 / 0.075 0.072 / 0.075 0.072 / 0.075 0.081 / 0.085
Heating kW 0.065 / 0.069 0.065 / 0.069 0.065 / 0.069 0.074 / 0.079
Current Cooling A 0.36 / 0.37 0.36 / 0.37 0.36 / 0.37 0.40 / 0.42
Heating A 0.30 / 0.32 0.30 / 0.32 0.30 / 0.32 0.34 / 0.37
External Finish (Munsell No.) Unit Galvanised Steel Plate
Panel Pure White (6.4Y 8.9/0.4)
Dimension
H x W x D
Unit mm 290 x 776 x 634
Panel mm 20 x 1080 x 710
Net Weight Unit kg 23 24
Panel kg 6.5 (15)
Heat Exchanger Cross Fin
Fan Type x Quantity Turbo Fan x 1
Air Flow Rate *2
(Lo-Mid-Hi)
m³/min 6.5-8.0-9.5 7.0-8.5-10.5
L/s 108-133-158 117-142-175
cfm 230-283-335 247-300-371
External Static
Pressure Pa 0
Motor Type 1-Phase Induction Motor
Output kW 0.015 (at 240V)
Air Filter PP Honeycomb Fabric (Long Life Type)
Refrigerant Pipe
Diameter
Gas (Flare) mm (in.) ø12.7 (ø1/2) (ø1/2)
Liquid (Flare) mm (in.) ø6.35 (ø1/4) (ø1/4)
Field Drain Pipe Diameter mm (in.) O.D.32 (1-1/4)
Sound Pressure
Level *2 *3
(Lo-Mid-Hi)
220V, 240V dB(A) 27-30-33 29-33-36
230V dB(A) 28-31-34 30-34-37
Notes:
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling : Indoor 27°C DB/19°C WB, Outdoor 35°C DB
Heating : Indoor 20°C DB, Outdoor 7°C DB/6°C WB
SPECIFICATIONS
INDOOR UNIT - CEILING CASSETTE TYPE
PLFY-P VLMD-E / 2-Way Airflow
Model PLFY-P50VLMD-E PLFY-P63VLMD-E PLFY-P80VLMD-E PLFY-P100VLMD-E PLFY-P125VLMD-E
Power Source 1-Phase 220-240V 50Hz / 1-Phase 220-230V 60Hz
Cooling Capacity*1 kW 5.6 7.1 9.0 11.2 14.0
BTU/h 19,100 24,200 30,700 38,200 47,800
Heating Capacity*1 kW 6.3 8.0 10.0 12.5 16.0
BTU/h 21,500 27,300 34,100 42,700 54,600
Power
Consumption
Cooling kW 0.082 / 0.086 0.101 / 0.105 0.147 / 0.156 0.157 / 0.186 0.28 / 0.28
Heating kW 0.075 / 0.080 0.094 / 0.099 0.140 / 0.150 0.150 / 0.180 0.27 / 0.27
Current Cooling A 0.41 / 0.43 0.49 / 0.51 0.72 / 0.74 0.75 / 0.88 1.35 / 1.35
Heating A 0.35 / 0.38 0.43 / 0.46 0.66 / 0.69 0.69 / 0.83 1.33 / 1.33
External Finish (Munsell No.) Unit Galvanised Steel Plate
Panel Pure White (6.4Y 8.9/0.4)
Dimension
H x W x D
Unit mm 290 x 946 x 634 290 x 1446 x 634 290 x 1708 x 606
Panel mm 20 x 1250 x 710 20 x 1750 x 710 20 x 2010 x 710
Net Weight Unit kg 27 28 44 47 56
Panel kg 7.5 12.5 13.0
Heat Exchanger Cross Fin
Fan Type x Quantity Turbo Fan x 1 Turbo Fan x 2 Sirocco Fan x 4
Air Flow Rate *2
(P50~P100:Lo-Mid-Hi)
(P125:Lo-Mid2-
Mid1-Hi)
m³/min 9.0-11.0-12.5 11.0-13.0-15.5 15.5-18.5-22.0 17.5-21.0-25.0 24.0-27.0-30.0-33.0
L/s 150-183-208 167-217-258 258-308-367 292-350-417 400-450-500-550
cfm 318-388-441 353-459-547 547-653-777 618-742-883 848-953-1,059-1,165
External Static
Pressure Pa 0
Motor Type 1-Phase Induction Motor
Output kW 0.020 (at 240V) 0.020 x 2 (at 240V) 0.030 x 2 (at 240V) 0.078 x 2 (at 240V)
Air Filter
PP Honeycomb Fabric (Long Life Type)
Synthetic Fibre
Unwoven
Cloth Filter (Long Life)
Refrigerant Pipe
Diameter
Gas (Flare) mm (in.) ø12.7 (ø1/2) ø15.88 (ø5/8)
Liquid (Flare) mm (in.) ø6.35 (ø1/4) ø9.52 (ø3/8)
Field Drain Pipe Diameter mm (in.) O.D.32 (1-1/4)
Sound Pressure
Level *2 *3
(Lo-Mid-Hi)
220V, 240V dB(A) 31-34-37 32-37-39 33-36-39 36-39-42 40-42-44-46
(Lo-Mid2-Mid1-Hi)
230V dB(A) 32-35-38 33-38-40 34-37-40 37-41-43
*2 Air flow rate/sound pressure level are in (Lo-Mid-Hi) or (Lo-Mid2-Mid1-Hi).
*3 It is measured in anechoic room. 123


Produktspezifikationen

Marke: Mitsubishi
Kategorie: Klimaanlage
Modell: PAR-U02MEDA ME

Brauchst du Hilfe?

Wenn Sie Hilfe mit Mitsubishi PAR-U02MEDA ME benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Klimaanlage Mitsubishi

Bedienungsanleitung Klimaanlage

Neueste Bedienungsanleitung für -Kategorien-