INSTRUCTION MANUAL
Français pg. 25
Español pg. 13
ENGLISH
HVNCVT2
Broad-Range High-Voltage
Non-Contact Tester
• tESt
• 240V
• 4.2kV
• 15kV
• 25kV
• 35kV
• 69kV
• 115kV
• 230kV
2
SYMBOLS
Warning or Caution
Risk of Electrical Shock
Double Insulated
GENERAL SPECIFICATIONS
The Broad-Range High-Voltage Non-Contact Tester (HVNCVT2) is an instrument
for verifying the live or de-energized status of conductors and other exposed
electrical equipment. The tester warns against dangerous voltage in several different
ranges without contacting the energized conductor. Only use with hot sticks and
rubber gloves meeting industry standards. Verify the rotary switch setting before
measuring voltage, to ensure it is on the correct setting for your application.
Always follow approved work safety practices and clearances per OSHA Sub-parts
R & V and all company work rules. For Minimum Approach Distances (MAD), see
OSHA Tables R-6 and R-7 (pages 8 & 9) in this manual.
• Operating Temperature: 14° to 122°F (-10° to 50°C) @ 85% relative humidity
• Storage Temperature: -4° to 140°F (-20° to 60°C) @ 85% relative humidity
• Dimensions: Tester: 10" x 4.25" x 4.25" (254 x 108 x 108 mm)
Case: 13.5" x 8.75" x 4.75" (343 x 222 x 121 mm)
• Weight: 1.32 lbs. (600 g)
• Power Source: Three 1.5V "C" cell batteries
Specifications subject to change.
ENGLISH
3
WARNINGS
To ensure safe operation and service of the tester, follow these instructions.
Failure to observe these warnings can result in severe injury or death.
• Use extreme caution when testing live electrical circuits due to risk of injury from
electrical shock.
• Always use hot sticks and rubber gloves meeting industry standards.
• Follow approved work safety practices and clearances per OSHA Sub-parts
R & V and your company work rules.
• Always test on a known live circuit to verify tester functionality prior to use.
• Do not exceed the limits marked on the instrument itself. Never test voltage
more than 230kV AC RMS.
• Never ground yourself when taking measurements. Do not touch exposed
circuit elements.
• Observe the proper safety precautions when working with voltage above 30V AC
RMS to avoid electrical shock hazard.
• Do not assume equipment or conductors are, or will remain, de-energized.
Always install proper grounding devices before starting procedure.
• Do not operate tester in an explosive atmosphere.
• Do not expose tester to rain or moisture. This increases the risk of fire
or electric shock.
• Do not rely on this tester for shielded wire or cable with concentric neutrals.
• Do not let the unit make contact with live line voltage. Do not touch any exposed
wiring, connections or other energized parts of an electrical circuit.
• 3-phase feeder cables with conductors close to each other may self-cancel the
electric field and not be detected by the device. Verify that the phase conductors
are separated by at least 15" (381 mm) before testing for AC voltage.
• Do not use in an area with mixed high voltages. In the presence of mixed
voltages, the tester may become unreliable.
• Always ensure tester is directly under the conductor being tested. If other live
voltage is nearby, tester may detect adjacent voltage.