IFM E84036 Bedienungsanleitung


Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für IFM E84036 (2 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 7 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
ifm electronic Gmbh
Friedrichstraße 1
45128 Essen
Germany
The information in this document is believed to be accurate and reliable and may change without notice.
EN E84036 Installation Manual Power Supply 3-Phase, 24V, 40A, 960W
DE E84036 Installationsanleitung Stromversorgung 3-Phase, 24V, 40A, 960W
FR E84036 Manuel d'installation Alimentation d'Énergie 3-Phase, 24V, 40A, 960W
ES E84036 Manual de instalación Fuente De Alimentación 3-Phase, 24V, 40A, 960W
IT E84036 Manuale di Installazione Gruppo di alimentazione 3-Phase, 24V, 40A, 960W
PT E84036 Manual de instalação Fonte De Alimentação 3-Phase, 24V, 40A, 960W
Doc. ID: PU-374.015.22-xxA (2021-04-05-MW2)
DIS-Nr.: 11396836 / 00
Read this first! English
Vor Inbetriebnahme lesen! Deutsch
Before operating this device, please read this manual thoroughly and retain this manual for
future reference! This device may only be installed and put into operation by qualified
personnel. If damage or malfunction should occur during operation, immediately turn power
off and send device to the factory for inspection. The device does not contain serviceable
parts. The information presented in this document is believed to be accurate and reliable and
may change without notice. For any clarifications the English translation will be used.
Bitte lesen Sie diese Warnungen und Hinweise sorgfältig durch, bevor Sie das Gerät in Betrieb
nehmen. Bewahren Sie die Anleitung zum Nachlesen auf. Das Gerät darf nur durch
fachkundiges und qualifiziertes Personal installiert werden. Bei Funktionsstörungen oder
Beschädigungen schalten Sie sofort die Versorgungsspannung ab und senden das Gerät zur
Überprüfung ins Werk. Das Gerät beinhaltet keine Servicebauteile. Die angegebenen Daten
dienen allein der Produktbeschreibung und sind nicht als zugesicherte Eigenschaften im
Rechtssinne aufzufassen. Im Zweifelsfall gilt der englische Text.
WARNING Risk of electrical shock, fire, personal injury, or death: WARNUNG
Missachtung nachfolgender Punkte kann einen elektrischen
Schlag, Brände, schwere Unfälle oder Tod zur Folge haben:
- Turn power off before working on the device. Protect against inadvertent re-powering.
- Do not open, modify or repair the device.
- Use caution to prevent any foreign objects from entering the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on and immediately after power-off. Hot surfaces may cause
burns.
- Schalten Sie die Eingangsspannung vor Installations-, Wartungs- oder Änderungsarbeiten
ab und sichern Sie diese gegen unbeabsichtigtes Wiedereinschalten.
- Führen Sie keine Änderungen oder Reparaturversuche am Gerät durch. Gerät nicht öffnen!
- Verhindern Sie das Eindringen von Fremdkörpern, wie z.B. Büroklammern und Metallteilen.
- Betreiben Sie das Gerät nicht in feuchter Umgebung oder in einer Umgebung, bei der mit
Betauung oder Kondensation zu rechnen ist.
- Gehäuse nicht während des Betriebes oder kurz nach dem Abschalten berühren. Heiße
Oberflächen können Verletzungen verursachen.
A lire avant mise sous tension! Français
Lea primero! Español
Veuillez lire ces instructions de montage et d'entretien avant de mettre l'alimentation sous
tension. Conservez ce manuel qui vous sera toujours utile. Cette alimentation ne doit être
installée que par du personnel qualifié et compétent. En cas de dommage ou
dysfonctionnement, coupez immédiatement la tension d’alimentation et retournez l’appareil à
l’usine pour vérification. ! L’alimentation ne contient pas de pièces échangeables Les
données indiquées dans ce document servent uniquement à donner une description du
produit et n'ont aucune valeur juridique. En cas de divergences, le texte anglais fait foi.
Conserve este manual como referencia para futuras consultas. La fuente de alimentación solo
puede ser instalada y puesta en funcionamiento por personal cualificado. Por favor lea
detenidamente este manual antes de conectar la fuente de alimentación. Si se produce un fallo
o mal funcionamiento durante la operación, desconecte inmediatamente la tensión de
alimentación. En ambos casos, el equipo debe ser inspeccionado en fábrica. La información
presentada en este documento es exacta y fiable en cuanto a la descripción del producto y
puede cambiar sin aviso. En casa de duda, prevalece el texto inglés.
AVERTISSEMENT Prendre en compte les points suivants, afin
d'éviter toute détérioration électrique, incendie,
dommage aux personnes ou mort: ADVERTENCIA Riesgo de descarga eléctrica, incendio, accidente
grave o muerte:
- Mettre l’alimentation hors tension avant toute intervention sur celle-ci et s'assurer qu'il n'y
a pas risque de redémarrage.
- Ne pas ouvrir, modifier ou réparer l'alimentation.
- Veiller à ce qu'aucun objet ne rentre en contact avec l'intérieur de l'alimentation
(trombones, pièces métalliques).
- Ne pas faire fonctionner l'appareil dans un environnement humide ou dans un
environnement où il peut y avoir de la condensation.
- Ne pas toucher le carter pendant le fonctionnement ou directement après la mise hors
tension. Surface chaude risquant d’entraîner des blessures.
- Desconectar la tensión de red antes de trabajar en la fuente de alimentación. Evite una
posible reconexión involuntaria.
- No realizar ninguna modificación o reparación de la unidad. No abrir la unidad.
- Evitar la introducción en la carcasa de objetos extraños.
- No usar el equipo en ambientes húmedos. No operar el equipo en ambientes donde se
espere la formación de rocío o condensación.
- No tocar durante el funcionamiento ni inmediatamente después del apagado. El calor de la
superficie puede causar quemaduras graves.
Leggere prima questa parte! Italiano
Leia primeiro! Portuguès
Prima di collegare il sistema di alimentazione elettrica si prega di leggere attentamente le
seguenti avvertenze. Conservare le istruzioni per la consultazione futura. Il sistema di
alimentazione elettrica deve essere installato solo da personale competente e qualificato. Se
durante il funzionamento si verificano anomalie o guasti, scollegare immediatamente la
tensione di alimentazione. In entrambi i casi è necessario far controllare l'apparecchio dal
produttore! I dati sono indicati solo a scopo descrittivo del prodotto e non vanno considerati
come caratteristiche garantite dell'apparecchio. In caso di differenze o problemi è valido il
testo inglese
Recomendamos a leitura cuidadosa das seguintes advertências e observações, antes de
colocar em funcionamento a fonte de alimentação. Guarde as Instruções para futura consulta,
em casos de dúvida. A fonte de alimentação deverá ser instalada apenas por profissionais da
área, tecnicamente qualificados. Se por acaso, durante a utilização ocorrer algum defeito de
funcionamento ou dano, desligue imediatamente a tensão de alimentação. Em ambos os casos,
será necessária uma verificação na Fábrica! Os dados mencionados têm como finalidade
somente a descrição do produto, e não devem ser interpretados como propriedades garantidas
no sentido jurídico. Em caso de duvidas aplica-se o texto em inglês.
AVVERTENZA Il mancato rispetto delle seguenti norme può
provocare folgorazione elettrica, incendi, gravi
incidenti e perfino la morte:
ATENÇÃO A não observância ou o incumprimento dos pontos a seguir
mencionados, poderá causar uma descarga elétrica, incêndios,
acidentes graves ou morte:
- Prima di eseguire interventi di installazione, di manutenzione o di modifica scollegare la
tensione di rete ed adottare tutti i provvedimenti necessari per impedirne il ricollegamento
non intenzionale.
- Non tentare di aprire, di modificare o di riparare da soli l'apparecchio.
- Impedire la penetrazione di corpi estranei nell'apparecchio, ad esempio fermagli o altri
oggetti metallici.
- Non far funzionare l'apparecchio in un ambiente umido. Non far funzionare l'apparecchio
in un ambiente soggetto alla formazione di condensa o di rugiada.
- Non toccare quando acceso e subito dopo lo spegnimento. La superficie calda può
causare scottature.
- Antes de trabalhos de instalação, manutenção ou modificação, desligue a tensão de
alimentação, protegendo-a contra uma nova ligação involuntária.
- Não efectue nenhuma modificação ou tentativa de reparação no aparelho. Quando
necessário contacte o seu distribuidor. Não abra o aparelho.
- Proteger a fonte de alimentação contra a introdução inadvertida de corpos metálicos, como
por ex., clipes ou outras peças de metal.
- Não usar o aparelho em ambientes húmidos. Não usar o aparelho em ambientes propensos
a condensações.
- Não tocar enquanto estiver em funcionamento, nem após a desligar. A superficie poderá
estar quente e provocar lesões.
EN E84036 Installation Manual
Product Description
The E84036 is a DIN-rail mountable power supply for three-phase mains systems, which provides a
floating, stabilized and galvanically separated SELV/PELV output voltage.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring, measurement equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or
threaten human life without additional appropriate safety devices, that are suited for the end-
application.
If this device is used in a manner outside of its specification, the protection provided by the device may
be impaired.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the
input terminals. Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids.
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1.
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use
without a proper PE (Protective Earth) connection.
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage
between the input terminals and the PE potential must not exceed 576Vac. The device is not designed
to be used on corner grounded delta systems.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device
is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including unlimited inductive or capacitive loads.
Do not apply return voltages from the load to the output terminals higher than 35V.
The output voltage can be adjusted with a small flat-blade screwdriver behind the flap on the front.
The green DC OK LED reports an output voltage above 90% of the adjusted voltage of a running
device.
The DC OK relay monitors the output voltage and the contact is closed when the DC OK LED is on.
Contact ratings: 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A for resistive loads.
The red overload LED is on when the output voltage falls below 90% of the adjusted value or in case
of a short circuit in the output. The LED is flashing, when the device has switched off due to over-
temperature or when the “Remote OFF” signal is activated. Input voltage is required.
The device is equipped with an over-temperature protection. In case of a high temperature, the output
shuts down and starts automatically again after cooling off.
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to
exceed +60°C. The output voltage of all devices shall be adjusted to the same value (±100mV) in
“Single Use” mode with the same load conditions on all units, or the units can be left with the factory
settings. After the adjustments, set the unit to Parallel Use” mode, in order to achieve load sharing.
The “Parallel Use” mode regulates the output voltage in such a manner that the voltage at no load is
approx. 4% higher than at nominal load. If more than three devices are connected in parallel, a diode,
fuse or circuit breaker with a rating of 50 or 63A is required on each output.
Same devices can be connected in series for higher output voltages. It is allowed to connect as many
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output
shuts down and automatically attempts to restart.
The device is equipped with a remote ON/OFF function to turn the output off. For this connect pin 15
with pin 16.
The output voltage can be remotely adjusted between 14 and 28Vdc by applying a control voltage
between pin 15 and the (-) terminal.
Technical Data
All values are typical figures specified at 3x 400Vac 50Hz input voltage,
symmetrical phase voltages, 24V, 40A output load, 25°C ambient
temperature and after a 5 minutes run-in time unless otherwise noted.
Output voltage DC 24V Nominal
Adjustment range 24 – 28Vdc Factory setting 24.1V
Output current Continuous:
40 – 34.3A Below +60°C ambient
30 – 25.7A At +70°C ambient
Short-term, up to 4s:
60 – 51.5A Below +70°C ambient
Derate linearly between +60°C and +70°C
Input voltage AC 3AC 380 - 480V -15% / +20%
Mains frequency 50 – 60Hz ±6%
Input current AC 1.65 / 1.35A At 3x400 / 480Vac
Power factor 0.88 / 0.90 At 3x400 / 480Vac
Input inrush current 4.5 / 4.5A peak At 3x400 / 480Vac,
temp. independent
Efficiency 95.3 / 95.2% At 3x400 / 480Vac
Losses 47.3 / 48.4W At 3x400 / 480Vac
Hold-up time 25 / 25ms At 3x400 / 480Vac
Temperature range -25 to +70°C
Max. wire size (litz wire) 4mm² For input terminals
Wire size AWG AWG 20-10 For input terminals
Max. wire diameter 2.8mm For input terminals
Wire stripping length 7mm / 0.28inch For input terminals
Tightening torque 1Nm / 9lb.inch For input terminals
Max. wire size (litz wire) 10mm² For output terminals
Wire size AWG AWG 22-8 For output terminals
Max. wire diameter 5.2mm For output terminals
Wire stripping length 12mm / 0.5inch For output terminals
Tightening torque 2.3Nm / 20lb.inch
For output terminals
Max. wire size (litz wire) 1.5m For signal terminals
Wire size AWG AWG 26-14 For signal terminals
Max. wire diameter 1.5mm For signal terminals
Wire stripping length 7mm / 0.28inch For signal terminals
Size (wxhxd) 110x124x127mm Without DIN-rail
Weight 1500g / 3.3lb
Functional Diagram
L2
L3
L1
+
+
-
-
Output
Over-
Voltage
Protection
PFC
Converter Power
Converter
Output
Filter
Output
Power
Manager
Temper-
ature
Shut-
down
Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter
DC-OK
LED
Remote ON/OFF
Voltage control
ON/
OFF
15
16
Overload
LED
DC-OK
Contact
DC-ok
Relay
13
14
V
OUT
Output
Voltage
Regulator
Single /
Parallel
Event Datalogger
Output Characteristic
Output voltage in single mode
70A
24V
Output current
12V
0V
10A 30A 40A 50A0A
Adjustment range
28V
20A 60A
B
A
A: continuous
B: for 4s
Temperature Range
Allowed output current at 24V
Ambient temperature
0A
-25
A: continuous
B: short term (typ. 4s)
60A
0 +70°C
30A
B
40A
+60
A


Produktspezifikationen

Marke: IFM
Kategorie: Nicht kategorisiert
Modell: E84036

Brauchst du Hilfe?

Wenn Sie Hilfe mit IFM E84036 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert IFM

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-