Hager HIC412E Bedienungsanleitung

Hager Schalter HIC412E

Lesen Sie kostenlos die ๐Ÿ“– deutsche Bedienungsanleitung fรผr Hager HIC412E (6 Seiten) in der Kategorie Schalter. Dieser Bedienungsanleitung war fรผr 17 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/6
1 6LE001133A.d
6LE001133A.d
HIC4xxE
Preliminary operations
Check the following upon delivery and after removal
of the packaging:
โ€ข Packaging and contents are in good condition.
โ€ข The product reference corresponds to the order.
โ€ข Contents should include:
- 1 x motorised changeover switch
- 1 x emergency handle and ๏ฌ xing clip
- 1 x quickstart instruction sheet.
Accessories
โ€ข Bridging bars and connection kits.
โ€ข Terminal shrouds.
โ€ข Terminal shield.
โ€ข Voltage sensing kit.
โ€ข HZI911 interface.
โ€ข Current transformers.
โ€ข Plug-in optional modules: RS485 MODBUS
communication, 2 inputs/2 outputs, Ethernet
communication, Ethernet communication +
RS485 JBUS/MODBUS gateway, Analogue
outputs, Pulse outputs.
This quick start is intended for personnel trained in
the installation and commissioning of this product.
For further details refer to the product instruction
manual available on the hager website.
โ€ข This product must always be installed and
commissioned by quali๏ฌ ed and approved
personnel.
โ€ข Maintenance and servicing operations should be
performed by trained and authorised personnel.
โ€ข Do not handle any control or power cables
connected to the product when voltage may be,
or may become present on the product, directly
through the mains or indirectly through external
circuits.
โ€ข Always use an appropriate voltage detection
device to con๏ฌ rm the absence of voltage.
โ€ข Ensure that no metal objects are allowed to fall
in the cabinet (risk of electrical arcing).
Failure to observe good enginering practises as
well as to follow these safety instructions may
expose the user and others to serious injury or
death.
Installation and commissioning
Clip for
storage
of the
emergency
handle
Risk of electrocution, burns or injury to
persons and/or damage to equipment.
Risk of damaging the device.
In case the product is dropped or
damaged in any way it is recommended
to replace the complete product
.
Step 1
Cabinet/
Back Plate
Installation
Step 2
Connecting the
power section
Step 3
COMMAND/
CONTROL
terminal
connections
Step 4
Power SUPPLY
and controller
terminal
connections
Step 5
Check
Step 6
Programming
Step 7A
AUT Mode
(Automatic
Control)
Step 7B
AUT Mode
(Remote
Control)
Step 7C
Emergency
Manual
Operation
Step 7D
Padlocking
zMotorised source changeover switch
125A - 630A
2. Power terminal connections
Use terminal lugs, rigid or ๏ฌ‚ exible busbars.
2 6LE001133A.d
Orientation
Recommended OK
OK NO
M
Fix. 195
Fix. 180
==
J1
UT C21
ร˜7
ร˜9
Fix. 180
Fix. 195
Dimensions in mm
125A 160A 200A 250A 315A 400A 500A 630A
Minimum Cu
cable section
at Ith
(mm2) 35 50 95 120 185 2 x 95 2 x 120
Minimum Cu
busbar section
at Ith
(mm2) - 2 x 30 x 5 2 x 40 x 5
Maximum Cu
cable section (mm2) 50 95 120 150 240 2 x 185 2 x 300
Maximum Cu
busbar width (mm) 25 32 50
Type of screw M8 M10 M12
Recommended
tightening
torque
(N.m) 8,3 20 40
Maximum
tightening
torque
(N.m) 13 26 45
125A 160A 200A 250A 315A 400A 500A 630A
4P
J1 34 35 34
M150 210 270
T36 50 65
C244 320
U20 25 35 32 45
W9 11 13
CA 10 15 20
CA
W
U
1. Installation
Ensure that the product is installed
on a ๏ฌ‚at rigid surface.
4.
3.
Door cut-out for front panel
50.5
20
138
165
3. CONTROL/COMMAND terminals
Ensure that the product is in Manual Mode.
3 6LE001133A.d
1 Preferred source
2 Alternate source
& Position 0 order
รฉ Position 1 order
" Position 2 order
' Zero position priority order
( Remote control enable (priority over auto)
ยง Product available output (Motor)
รจ Position II aux contact
! Position I aux contact
รง Position 0 aux contact
a O/P to HZI911 remote display
z Programmable output contact, by default set
to ATS product available - Normally open
e y to programmable inputs 1-4
u i and programmable inputs 5-6
o Aux. supply (207/210) to be used with
optional I/O modules
p Contact โ€œStart/Stop Gensetโ€: if S1 is not
available the NC contact (71-72) is closed
q Contact โ€œStart/Stop Gensetโ€: if S1 is not
available the NO contact (71-74) is open
s Option module slots 1 to 4
d Current Transformer incoming cable
connections
f Voltage sensing inputs
g Power supply inputs
Example: control wiring for a 400 VAC application having a 3 phase and neutral supply
f f
gg
HZI911
4. Power supply, sensing and control wiring
Use cables with 1,5 to 2,5 mm2 section. Screw M3 Tightening torque: min.: 0.5 Nm - max.: 0.6 Nm
+=,๎˜œ๎˜”๎˜”
๎˜™๎˜—% ๎˜™๎˜–% ๎˜—๎˜”๎˜š ๎˜—๎˜”๎˜™ ๎˜—๎˜”๎˜˜ ๎˜—๎˜”๎˜— ๎˜—๎˜”๎˜–
3RZHU๎˜ƒ๎˜ƒ๎˜•๎˜“๎˜›๎˜๎˜•๎˜š๎˜š9a๎˜ƒ๎˜Ž๎˜’๎˜๎˜•๎˜“๎˜ˆ
๎˜•๎˜“๎˜š ๎˜•๎˜“๎˜› ๎˜•๎˜“๎˜œ ๎˜•๎˜”๎˜“ ๎˜š๎˜”๎˜š๎˜• ๎˜š๎˜—
3RZHU๎˜ƒ๎˜ƒ๎˜•๎˜“๎˜›๎˜๎˜•๎˜š๎˜š9a๎˜ƒ๎˜Ž๎˜’๎˜๎˜•๎˜“๎˜ˆ
ATS Power supply input II
Power supply II - L
Power supply II - N
208-277 VAC ยฑ20% : 50/60 Hz
ATS Voltage sensing input
Source supply II
S II - Phase 1
S II - Phase 2
S II - Phase 3
575 VAC (ph-ph) maxi
S II - Neutral
332 VAC (ph-n) maxi
Programmable inputs
To option module (-)/Common
Progr. inputs (208-209)
To option module (+)
Genset Start/stop
NC
Common
NO
ATS Power supply input I
Power supply I - L
Power supply I - N
208-277 VAC ยฑ20% : 50/60 Hz
ATS Voltage sensing input
Source supply I
S I - Phase 1
S I - Phase 2
S I - Phase 3
575 VAC (ph-ph) maxi
S I - Neutral
332 VAC (ph-n) maxi
ATS Module control inputs
(programmable)
ATS Module output control
(programmable)
Remote interface
RJ45 to HZI911
Current transformer incoming
cable connections
Slot for optional modules
5. Check
Whilst in manual mode,
check the wiring
and if ok power up
the product.
LED Green =
โ€œPowerโ€๎™ฝ: ON
LED Red =
โ€œManuel/Defautโ€: ON


Produktspezifikationen

Marke: Hager
Kategorie: Schalter
Modell: HIC412E

Brauchst du Hilfe?

Wenn Sie Hilfe mit Hager HIC412E benรถtigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Schalter Hager

Bedienungsanleitung Schalter

Neueste Bedienungsanleitung fรผr -Kategorien-