Festo VPEV-1/8-M12 Bedienungsanleitung

Festo Nicht kategorisiert VPEV-1/8-M12

Lesen Sie kostenlos die 📖 deutsche Bedienungsanleitung für Festo VPEV-1/8-M12 (2 Seiten) in der Kategorie Nicht kategorisiert. Dieser Bedienungsanleitung war für 9 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet

Seite 1/2
VPEV-x-M12
Festo SE & Co. KG
Postfach
73726 Esslingen
+49 711 347-0
www.festo.com
Bedienungsanleitung
Operating instructions
指南
8048534
1509c
[8048535]
Original: de
Zur Einhaltung der Zertifizierungsbedingungen von
Underwriters Laboratories Inc. (UL) beachten Sie fol
gende englischsprachige Hinweise für USA und Kanada:
To ensure compliance with the Underwriters Labora
tories Inc. (UL) approval conditions for USA and Canada,
please note the following notices in English:
Only for use in Class 2 Circuits.
This device is intended to be used with a Class 2 power
source or NEC Class 2 transformer in accordance with
UL1310 or UL1585.
As an alternative a LV/C (Limited Voltage / Current)
power source with one of the following properties can
be used:
An isolating device such that the maximum open
circuit voltage potential available to the circuit is not
more than 30 Vac or 42.2 Vdc and the current is
limited to a value not exceeding 8 amperes measured
after 1 minute of operation.
A suitable isolating source in conjunction with a fuse
in accordance with UL248. The fuse shall be rated
max. 3.3 A (ac circuits max. 30 Vac) or 2.3 A (dc cir
cuits max. 42.4 Vdc) and be installed in the 30 Vac or
42.2 Vdc power supply to the device in order to limit
the available current.
Note that, when more than one power supply or
isolating device is used, connection in parallel is not
permitted.
5
4
1
2
3
SW11
8
6
6
7
Fig. 1
Einstellbereich bei Einsatz als Vakuumschalter
Adjusting range if used as a vacuum switch
Einstellbereich bei Einsatz als Druckschalter
Adjusting range if used as a pressure switch
Fig. 2
Vakuumschalter VPEV-x-M12 de.......................
1 Anwendung
Der Vakuumschalter VPEV dient bestimmungsgemäß zur
Überwachung von Druckveränderungen im Drucklei
tungssystem. Der VPEV öffnet oder schließt einen elek
trischen Stromkreis beim Erreichen eines einstellbaren
Druckwertes. Die oberen und unteren Schaltpunkte sind
voneinander unabhängig einstellbar.
2 Voraussetzungen für den Produkteinsatz
Hinweis
Einbau und Inbetriebnahme nur von qualifiziertem
Fachpersonal, gemäß Bedienungsanleitung. Diese
Produkte sind ausschließlich zur Verwendung mit
Druckluft vorgesehen. Andere Medien auf Anfrage.
Durch unsachgemäße Handhabung entstehen
Fehlfunktionen.
Stellen Sie sicher, dass die Vorgaben dieses
Kapitels stets eingehalten werden.
Vergleichen Sie die Grenzwerte in dieser Bedienungs
anleitung mit denen Ihres Einsatzfalls (z. B. Drücke,
Kräfte, Momente, Temperaturen).
Behalten Sie das einmal gewählte Betriebsmedium
über die gesamte Produktlebensdauer bei.
Entfernen Sie die Verpackungen. Die Verpackungen
sind vorgesehen für eine Verwertung auf stofflicher
Basis (Ausnahme: Ölpapier = Restmüll).
Berücksichtigen Sie die Warnungen und Hinweise
am Produkt und
in dieser Bedienungsanleitung.
Verwenden Sie das Produkt im Originalzustand ohne
jegliche eigenmächtige Veränderung.
3 Einbau
3.1 Mechanisch
Wandbefestigung è Fig. 1
1. Stecken Sie zwei Schrauben M5 durch die Durch
gangsbohrungen 4.
2. Befestigen Sie den VPEV an der vorgesehenen Stelle.
Befestigung mit Montageplatte è Fig. 1
1. Montieren Sie den VPEV mit der Verschlussschraube
6 in den Druckluftanschluss Gx 5 an der Montage
platte 7.
3.2 Pneumatisch
1. Drehen Sie eine Verschraubung in den Vakuum-
anschluss Gx 8 . Anziehdrehmoment max. 20 Nm.
2. Verschlauchen Sie die Verschraubung mit einem
entsprechenden Schlauch.
Hinweis
Durch Umsetzen der Verschlussschraube 6 vom
Druckluftanschluss 5 in den Vakuumanschluss 8
kann der VPEV als Druckschalter (Kennlinie è Fig. 2)
eingesetzt werden.
3.3 Elektrisch
Verkabeln Sie die Anschlussdose wie folgt:
Pin-Nr. Anschlüsse Pin-Belegung
1 + []
2 Öffner
4 Schließer
Max. Anziehdrehmoment 0,5 Nm
4 Inbetriebnahme
Werkseinstellung
Unterer Schaltdruck -0,5 bar ±0,04 bar
Hysterese 0,3 bar ±0,06 bar
Einstellelemente
Schraube 2Unterer Schaltdruck
Bolzen 3Hysterese (oberer Schaltdruck =
unterer Schaltdruck + Hysterese)
Beachten Sie, dass die Schraube 2 nur beim Drehen
gegen den Uhrzeigersinn einen Anschlag hat.
Definition
Schaltverhalten eines Vakuumschalters è Fig. 2
oberer Schaltdruck: p1
unterer Schaltdruck: p2
– Hysterese: Hy
Zur Schaltpunkteinstellung des VPEV è Fig. 1
1. Verkabeln Sie die elektrischen Anschlüsse Pin 1 und
Pin 2 mit einem Durchgangsprüfer;
è Einbau elektrisch.
2. Entfernen Sie die Schutzkappe 1.
3. Drehen Sie die Schraube 2 entgegen dem Uhrzeiger
sinn bis zum Anschlag.
4. Beaufschlagen Sie den VPEV mit dem gewünschten
unteren Schaltdruck p2. Der Durchgangsprüfer geht
in Ausgangsstellung.
5. Drehen Sie die Schraube 2 im Uhrzeigersinn, bis der
VPEV schaltet. Der Durchgangsprüfer reagiert.
Der Schaltpunkt für den unteren Schaltdruck p2 ist
eingestellt.
Hinweis
Eine Umdrehung entspricht einer Veränderung des
Schaltdrucks von ca. 0,18 bar.
Hystereseeinstellung
p1 (-0,6 … -1,0 bar) p1 (-0,2 … -0,6 bar)
Bolzen 3 im Uhrzeigersinn bis
Anschlag drehen.
Bolzen 3 gegen den Uhrzeiger
sinn bis Anschlag drehen.
Hystereseeinstellung des VPEV è Fig. 2
6. Drehen Sie den Bolzen 3 im Uhrzeigersinn bis zum
Anschlag. Der Durchgangsprüfer bleibt unverändert.
7. Beaufschlagen Sie den VPEV mit dem oberen Schalt-
druck p1 (unterer Schaltdruck p2 plus gewünschte
Hysterese Hy è Fig. 2). Der Durchgangsprüfer bleibt
unverändert.
8. Drehen Sie den Bolzen 3 gegen den Uhrzeigersinn
bis der VPEV schaltet.
Der Durchgangsprüfer geht in Ausgangsstellung.
Der Schaltpunkt für den oberen Schaltdruck p1 ist
eingestellt.
Bei Bedarf einer Schaltpunktkorrektur:
Hinweis
Beim Drehen an der Schraube 2 nehmen die Schalt
punkte für den oberen und unteren Schaltdruck
gleichzeitig zu oder ab.
9. Wiederholen Sie die nachfolgenden Schritte, bis der
gewünschte obere und untere Schaltpunkt eingestellt
sind:
zuerst unteren Schaltdruck p2 anlegen und
Schraube 2 drehen, dann
oberen Schaltdruck p1 anlegen und Bolzen 3
drehen. Dadurch präzisieren Sie schrittweise
Schaltpunkt und Hysterese.
10. Befestigen Sie die Schutzkappe 1.
5 Bedienung und Betrieb
Hinweis
Druckänderungen müssen größer als 0,003 bar/s
sein, damit der Vakuumschalter sicher schaltet.
Bei Schwankungen der Mediumstemperatur:
Hinweis
Beachten Sie, dass der Schaltpunkt geringfügig
beeinflusst wird.
Bei Mediumstemperatur 1 °C:
Hinweis
Vermeiden Sie, dass der Taupunkt erreicht wird. Bei
Erreichen des Taupunkts vereist die Membrane und
wird steifer. Dadurch ändern sich die Kennwerte des
Vakuumschalters.
Abhilfe: Der Taupunkt kann durch getrocknete Druck
luft gesenkt werden.
Zum Ausgleich von Schaltpunktabweichungen bei hohen
Schaltspielzahlen:
Wiederholen Sie die Schaltpunkteinstellung
(è Inbetriebnahme).
6 Wartung und Pflege
Reinigen Sie bei Bedarf den VPEV außen mit einem
weichen Lappen. Zulässige Reinigungsmedien sind
alle werkstoffschonenden Medien.
7 Zubehör
Bezeichnung Typ
Montageplatte APL-2N-VPEV
8 Störungsbeseitigung
Störung Mögliche Ursache Abhilfe
VPEV schaltet
nicht
Schaltpunkt zu hoch Schaltpunkt korrigieren
(èInbetriebnahme)
Hysterese zu groß Hysterese bei Inbetrieb
nahme zunächst auf
Minimum einstellen
(èInbetriebnahme)
Schalter defekt VPEV zu Festo schicken
Schaltsignal
wird nicht
ausgegeben
Anschlussfehler Überprüfen Sie die
elektrische Anschluss
belegung des VPEV
9 Technische Daten
Typ VPEV-x-M12
Messverfahren Pneumatisch-elektrischer Druckwandler
Messgröße Relativdruck
Schaltelement 
funktion
Wechsler
Betriebsdruck -1 … 1,6 bar
Betriebsmedium Vakuum / gefilterte Druckluft, geölt oder
ungeölt, Filterfeinheit min. 40 μm
Einbaulage Beliebig
Pneumatischer An
schluss
Gx
Elektrischer An
schluss
Stecker M12x1, 4-polig, runde Bauform
nach EN 60947-5-2
Druckmessbereich -11,6 bar
Einstellbereich
Schwellwer te
Vakuum Schaltpunkt: -0,95 -0,2 bar
Vakuum Hysterese: 0,16 … 0,55 bar
Druckluft Schaltpunkt: 0,16 1,6 bar
Druckluft Hysterese: 0,2 0,7 bar
Mediumstemperatur -20+80 °C
Umgebungs
temperatur
-20+80 °C
Max. Schaltaus
gangsspannung AC
48 V
Max. Schaltaus
gangsspannung DC
48 V
Max. Schaltstrom 5 A (ohmsche Last)
(Bemessungsbetriebsstrom:
4 A ohmsche Last; 3 A induktive Last)
Mindestlaststrom 1 mA (DC/AC 24 V)
10 mA (DC/AC 10 V)
100 mA (DC/AC 5 V)
Zul. Kontakt-
belastung
Ohmsche Last: DC 30 V 5 A
Induktive Last: DC 30 V 3 A
Gebrauchskategorie AC 12/DC 12 (ohmsche Last)
AC 14/DC 13 (kleine elektromagnetische
Last und Elektromagnete)
Schaltzeit:
bei -0,8 bar Ein: 8 ms (typisch), Aus: 9 ms (typisch)
bei 1,6 bar Ein: 3 ms (typisch), Aus: 7 ms (typisch)
Schutzar t nach
EN 60529
IP65
Vacuum switch VPEV-x-M12 en........................
1 Application
The vacuum switch VPEV has been designed for monitor
ing changes in pressure in the compressed air system.
The VPEV opens or closes an electrical circuit when an
adjustable pressure value is reached. The upper and
lower switching points can be set independently of each
other.
2 Conditions of use
Note
Fitting and commissioning is to be carried out only by
qualified personnel in accordance with the operating
instructions. These products are designed to be
operated with compressed air only. Other media upon
request.
Incorrect handling can result in malfunctioning.
Ensure that the specifications in this chapter are
always observed.
Compare the limit values specified in these operating
instructions with your actual application (e.g. forces,
torques, temperatures).
Maintain the selected operating medium for the com
plete service life of the product.
Remove the packaging. The packing is intended for
recycling (except for: oiled paper = other waste).
Please observe the warnings and instructions:
on the product and
in these operating instructions.
Unauthorised product modification is not permitted.
3 Fitting
3.1 Mechanical
Wall mounting è Fig. 1
1. Insert two M5 screws through the holes 4.
2. Fasten the VPEV in the intended position.
Fastening with mounting plate è Fig. 1
1. Mount the VPEV on the mounting plate 7 by means
of a screw plug 6 in the compressed air port Gx 5 .
3.2 Pneumatic
1. Screw a fitting into the vacuum connection Gx 8 .
Max. tightening torque 20 Nm.
2. Connect the fitting with appropriate tubing.
Note
By moving the screw plug 6 from the compressed air
port 5 to the vacuum connection 8 it is possible to
use the VPEV as a pressure switch (characteristic
curve è Fig. 2).
3.3 Electrical fitting
Wire the connector socket as follows:
Pin no. Connections Pin assignment
1 + [–]
2 N/C contact
4 N/O contact
Max. tightening torque 0.5 Nm
4 Commissioning
Factory setting
Lower switching pressure -0.5 bar ±0.04 bar
Hysteresis 0.3 bar ±0.06 bar
Configuration components
Screw 2Lower switching pressure
Bolt 3Hysteresis (upper switching pressure =
lower switching pressure + hysteresis)
Note that the screw 2 has a stop only when it is
turned in an anti-clockwise direction.
Definition
Switching behaviour of a vacuum switch è Fig. 2
Upper switching pressure: p1
Lower switching pressure: p2
– Hysteresis: Hy
To set the switching point of the VPEV è Fig. 1
1. Wire the electrical connections pin 1 and pin 2 with a
continuity tester;
è Fitting electric components.
2. Remove protective cap 1.
3. Turn the screw 2 in an anti-clockwise direction as far
as possible.
4. Pressurize the VPEV with the desired lower switching
pressure p2. The continuity tester goes to its initial
position.
5. Turn the screw 2 in a clockwise direction until the
VPEV switches. The continuity tester reacts. The
switching point for the lower switching pressure p2
has now been set.
Note
One revolution corresponds to a modification of the
switching pressure of approx. 0.18 bar.
Setting the hysteresis
p1 (-0.6 … -1.0 bar) p1 (-0.2 … -0.6 bar)
Turn bolt 3 in a clockwise
direction as far as possible.
Turn bolt 3 in an anti- clockwise
direction as far as possible.
Setting the hysteresis of the VPEV è Fig. 2
6. Turn the bolt 3 in a clockwise direction as far as
possible. The continuity tester remains unchanged.
7. Pressurize the VPEV with the upper switching pres
sure p1 (lower switching pressure p2 plus desired
hysteresis Hy è Fig. 2). The continuity tester remains
unchanged.
VPEV-x-M12
Festo SE & Co. KG
Postfach
73726 Esslingen
+49 711 347-0
www.festo.com
Bedienungsanleitung
Operating instructions
指南
8048534
1509c
[8048535]
Original: de
To ensure compliance with the Underwriters Labora
tories Inc. (UL) approval conditions for USA and Canada,
please note the following notices in English:
Underwriters Laboratories Inc. (UL)
司的认证条 请注意 列对美国和加拿大的英
文注意:
Only for use in Class 2 Circuits.
This device is intended to be used with a Class 2 power
source or NEC Class 2 transformer in accordance with
UL1310 or UL1585.
As an alternative a LV/C (Limited Voltage/Current)
power source with one of the following properties can
be used:
An isolating device such that the maximum open
circuit voltage potential available to the circuit is not
more than 30 Vac or 42.2 Vdc and the current is
limited to a value not exceeding 8 amperes measured
after 1 minute of operation.
A suitable isolating source in conjunction with a fuse
in accordance with UL248. The fuse shall be rated
max. 3.3 A (ac circuits max. 30 Vac) or 2.3 A
(dccircuits max. 42.4 Vdc) and be installed in the
30 Vac or 42.2 Vdc power supply to the device in order
to limit the available current.
Note that, when more than one power supply or
isolating device is used, connection in parallel is not
permitted.
5
4
1
2
3
SW11
8
6
6
7
Fig. 1
Adjusting range if used as a vacuum switch
 真空开 用时的调节范围
Adjusting range if used as a pressure switch
 压力开 用时的调节范围
Fig. 2
8. Turn the bolt 3 in an anti-clockwise direction until the
VPEV switches.
The continuity tester goes to its initial position. The
switching point for the upper switching pressure p1
has now been set.
If correction of the switching point is necessary:
Note
When the screw 2 is turned, the switching points for
the upper and lower switching pressure increase or
decrease at the same time.
9. Repeat the following steps until the desired upper
and lower switching points are set:
first apply lower switching pressure p2 and turn
screw 2, then
apply upper switching pressure p1 and turn bolt
3. In this way you can define in steps the switch
ing point and the hysteresis.
10. Fasten the protective cap 1.
5 Operation
Note
Pressure changes must be greater than 0.003 bar/s
for the pressure switch to switch reliably.
If there are fluctuations in the medium temperature:
Note
Note that the switching point will be slightly
influenced.
If medium temperatures are 1 °C:
Note
Avoid the dew point being reached. If the dew point is
reached, the membrane will ice up and become stiff.
The characteristic values of the vacuum switch will
then be modified.
Remedy: The dew point can be lowered if dried
compressed air is used.
To compensate for deviations in the switching point after
a high number of switching cycles:
Repeat the switching point setting
(è Commissioning).
6 Care and maintenance
If the VPEV is dirty, clean the exterior with a soft cloth.
All non-abrasive cleaning agents are permitted.
7 Accessories
Description Type
Mounting plate APL-2N-VPEV
8 Eliminating faults
Fault RemedyPossible cause
VPEV does
not switch
Switching point too
high
Correct switching point
(èCommissioning)
Hysteresis too large When commissioning
set hysteresis at first at
minimum
(èCommissioning)
Switch defective Return VPEV to Festo
No switching
signal given
Connection fault Check the electrical
connection assignment
of the VPEV
9 Technical specifications
Type VPEV-x-M12
Method of measurement Pneumatic/electrical pressure
transducer
Measured variable Relative pressure
Switching element
function
Changeover switch
Operating pressure -1 … 1.6 bar
Operating medium Vacuum / filtered compressed air,
lubricated or unlubricated, min.
grade of filtration 40μm
Assembly position As desired
Pneumatic connection Gx
Electrical connection Plug M12x1, 4-pin, round design to
EN 60947-5-2
Pressure measuring
range
-1 … 1.6 bar
Threshold value setting
range
Vacuum switching point:
-0.95 … -0.2bar
Vacuum hysteresis: 0.16 0.55 bar
Compressed air switching point:
0.16 … 1.6 bar
Compressed air hysteresis:
0.2 0.7bar
Media temperature -20 … +80 °C
Ambient temperature -20 … +80 °C
Max. switch output
voltage AC
48 V
Max. switch output
voltage DC
48 V
Max. switching current 5 A (ohmic load)
(Rated operating current:
4 A ohmic load; 3 A inductive load)
Minimum load current 1 mA (DC/AC 24 V)
10 mA (DC/AC 10 V)
100 mA (DC/AC 5 V)
Permitted contact loading Ohmic load: DC 30 V 5 A
Inductive load: DC 30 V 3 A
Utilisation category AC 12/DC 12 (ohmic load)
AC 14/DC 13 (no electromagnetic
load and electromagnets)
Response time:
at -0.8 bar On: 8 ms (typical), off: 9 ms (typical)
at 1.6 bar On: 3 ms (typical), off: 7 ms (typical)
Protection class as
per EN 60529
IP65
 VPEV-x-M12 zh.......................
1
真空开 VPEV 按照规定用 监控压力管系统 的
压力变化 到设置的压力 打开或 VPEV
    电路 可单独调节 开 点和 开 点
2

 许由备资质的 员据操指南行安
装和调试 用压缩空气 质敬。   本 品 可 。
请垂询
操 当 引起功能故
请确 。始终守本章规定
请将本操   指南 的极您的 用情 行对
比 如 压力、 、扭矩温度等
请在   品整 用寿命期 只 用 种工
包装材料。 包装材料均可回收材料
( : 外 油纸 废料
请注意 列警告和注意 :
 品 和
本操 。指南
请您在原装状态 用本 品 行勿擅自
改动
3
3.1 
 è Fig. 1
1. M5 螺 穿  4
2. VPEV 固定在定 置 。
装 装进行 è Fig. 1
1.请 螺 堵头 6 VPEV 安装到安装板 7
的压缩空气 Gx 5 接口。
3.2 气动
1.请将螺纹接头旋真空接口 Gx 8
最大拧紧扭矩 20 Nm。
2.请将螺纹接头 接相应的气管

将压缩空气接口 5 6 的螺 堵头 换 真空
接口 8则可 压力开 特性曲线 VPEV 
è Fig. 2 。
3.3 
按表接 接插口
针 配  
1 + []
2触点
4常开触点
最大拧紧扭矩 0.5 Nm
4调试
!"#
 开 压力 -0.5 bar ±0.04 bar
0.3 bar ±0.06 bar
$%
螺 开2
螺栓 压力 压力 3 ( = +  )
请注意 2 只有在 时 旋转时才有止档
 。
&'
真空开 的开 特性 è Fig. 2
–  :压力 p1
–  :压力 p2
 :Hy
VPEV 的开 点设置 è Fig. 1
1.请您路检测接电接口 Pin 1
Pin 2
è电气安装
2.请移 护盖 1
3. 时 旋转螺2, 直至到 止挡 。
4.请 所 的 压力 p2 VPEV 行加压
 路检测器  。初始 置
5.请 时 旋转螺2, 直至 VPEV 行开。
路检测器 反应 。
  开 压力 p2 的开 点完成设置

旋转 圈对应的开 压力的变化约  0.18 bar
迟 设( #
p1 (-0.6 … -1.0 bar) p1 (-0.2 … -0.6 bar)
将螺栓 旋转至止档 3  
 。
将螺栓 旋转至止档 3  
 。
VPEV 滞设置 è Fig. 2
6.请 时 旋转螺栓 3 直至止档 置
路检测器  。持 变
7.压力 p1 VPEV 行加压( 
 。压力 p2 加所 的 滞 Hy è Fig. 2) 
检测器。持 变
8.请 时 旋转螺栓 3 直至 VPEV 行开。
 路检测器  。初始 置
  开 压力 p1 的开 点完成设置
必要时 行开 点 正

旋转螺2,  压力和的开
同时升 。
9.  列步 直到调整到所 点和
 :开 点
–  !施加 开 压力 p2 并旋转螺2
然后
施加 开 压力 p1 并旋转螺栓 3
此方法"步设置开 点和
10.固定护盖 1
5)*+运行

压力变化必# , 0.003 bar/s 安开真 
空开。
质温度波动时

请注意 受到 微的影响开 点  $
质温度 1 °C

%  &  & ,温度 到 点如果 到 点 薄膜 结并
变得 因此 真空开 的特征 发生 。 
变化
补救措施 用干燥的压缩空气 &
 , 行多次开可平衡开 点 差
请 复 行开点设置è 调试
6,-+./
 要时请用软布清洁 VPEV
所有无腐蚀性清洁剂'
7
01 2
安装板 APL-2N-VPEV
83 4障 除
356789 :;<
VPEV 无法开 开 点太开 点è调试
  滞 大 调试时,!滞设置
最小 调试 è
开 将损坏 VPEV 寄给 Festo
未发 接有误 检查 的电气 接情 VPEV
9=>?@
2 VPEV-x-M12
(方法 气动电子压力转换器
测 变( ( 相对压力
功能 转换
压力 -1 1.6 bar
工 质  真空/滤的压缩空气经润滑或未润滑
滤精度至少 40 μm
安装 置 意
气接口 Gx
电接口 插头 圆形结构形式 M12x14 , ,
符合 EN 60947-5-2
压力测 范围(-1 1.6 bar
) : 设置范围 真空开 点 -0.95 -0.2 bar
真空 :0.16 0.55 bar
压缩空气开0.16 1.6 bar
压缩空气 :0.2 0.7 bar
质温度 -20 +80 °C
环境温度 -20 +80 °C
最大的开 *
流电压
48 V
最大的开 *
直流电压
48 V
最大开 电流 5 A( +电 负,)
( :测定工电流
4 A 3 A 电 负+ ,; 感应负,)
最小负 电流,1 mA (DC/AC 24 V)
10 mA (DC/AC 10 V)
100 mA (DC/AC 5 V)
许的接触
,
电 负+ ,: 30 V DC 5 A
感应负,: 30 V DC 3 A
用类别 AC 12/DC 12( +电 负,)
AC 14/DC 13(- .)小的电磁负,和电磁
开 时:
-0.8 bar 开启: (8 ms ),
 :9 ms
1.6 bar 开启3 ms),
 :7 ms
/护等
EN 60529
IP65


Produktspezifikationen

Marke: Festo
Kategorie: Nicht kategorisiert
Modell: VPEV-1/8-M12

Brauchst du Hilfe?

Wenn Sie Hilfe mit Festo VPEV-1/8-M12 benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten




Bedienungsanleitung Nicht kategorisiert Festo

Bedienungsanleitung Nicht kategorisiert

Neueste Bedienungsanleitung für -Kategorien-