Eaton Powerware 9355-12-N-8-32x9Ah Bedienungsanleitung
Eaton
Unterbrechungsfreies Stromversorgungssystem
Powerware 9355-12-N-8-32x9Ah
Lesen Sie kostenlos die đ deutsche Bedienungsanleitung fĂŒr Eaton Powerware 9355-12-N-8-32x9Ah (50 Seiten) in der Kategorie Unterbrechungsfreies Stromversorgungssystem. Dieser Bedienungsanleitung war fĂŒr 21 Personen hilfreich und wurde von 2 Benutzern mit durchschnittlich 4.5 Sternen bewertet
Seite 1/50
Userâs Guide
UPS 8 â 15 kVA,
400 V 50/60 Hz output
(3-phase input/output)
©2007 Eaton Corporation
All Rights Reserved
The contents of this manual are the copyright of the publisher and
may not be reproduced (even extracts)
unless permission granted.
Every care has been taken to ensure the accuracy of
the information contained in this manual, but no liability
can be accepted for any errors or omission. The right
to make design modiïŹcations is reserved.
UPS 8 â 15 kVA, 400 V 50/60 Hz
Userâs Guide 1023625 revision C
Contents
1. Safety instructions ............................................................................................................................................................. 4
Audience .............................................................................................................................................................................. 4
CE marking ........................................................................................................................................................................... 4
User precautions ................................................................................................................................................................. 4
Environment ......................................................................................................................................................................... 5
Inquiries ................................................................................................................................................................................ 5
2. Mechanical installation .................................................................................................................................................... 6
Delivery check ..................................................................................................................................................................... 6
Unpacking and visual inspection ..................................................................................................................................... 6
3. Planning before installation ............................................................................................................................................. 8
4. Cabinet installation ............................................................................................................................................................ 9
Maintenance bypass switch ............................................................................................................................................. 9
Transformer option ............................................................................................................................................................. 11
External battery cabinet option ........................................................................................................................................ 12
Battery racks ....................................................................................................................................................................... 12
5. Electrical installation ........................................................................................................................................................ 13
Power cables and protective fuses ................................................................................................................................. 14
Wiring procedure ................................................................................................................................................................ 15
External Battery Cabinet (EBC) installation procedure ................................................................................................ 18
6. Software and connectivity ................................................................................................................................................ 20
Communication cables ....................................................................................................................................................... 20
Connection to the standard RS 232 port (X53)................................................................................................................ 20
LanSafe software ........................................................................................................................................................... 21
External control connections ............................................................................................................................................ 21
Emergency Power Off (EPO) ......................................................................................................................................... 23
Relay outputs ................................................................................................................................................................... 23
Programmable signal inputs ......................................................................................................................................... 23
XSlot communication (option) ........................................................................................................................................... 24
SNMP/Web Module (optional) ..................................................................................................................................... 24
AS400 Relay Module (optional) .................................................................................................................................... 25
Single Serial Port Module (optional) ........................................................................................................................... 25
Modus/Jbus Module (optional) .................................................................................................................................... 25
7. User operations ................................................................................................................................................................... 26
Display functions ................................................................................................................................................................. 26
User Settings ....................................................................................................................................................................... 27
ConïŹguring user settings .............................................................................................................................................. 29
Changing language ........................................................................................................................................................ 29
Changing charging current ........................................................................................................................................... 29
Using relay outputs ........................................................................................................................................................ 29
Normal start-up ................................................................................................................................................................... 30
Battery start-up ................................................................................................................................................................... 30
Start-up after EPO ............................................................................................................................................................... 30
Shutdown ............................................................................................................................................................................. 31
8. Maintenance ....................................................................................................................................................................... 32
Regular service/intervals ................................................................................................................................................... 32
Batteries ........................................................................................................................................................................... 32
Cooling fan ....................................................................................................................................................................... 33
LED Indicators ..................................................................................................................................................................... 33
Maintenance bypass switch (MBS) operation .............................................................................................................. 33
Turn UPS from normal mode to mechanical bypass ................................................................................................ 34
Turn UPS from mechanical bypass to normal mode ................................................................................................ 35
9. Parallel systems ................................................................................................................................................................. 37
Overview ............................................................................................................................................................................... 37
Tie cabinets .......................................................................................................................................................................... 38
XSlot Hot Sync card: installing and wiring ..................................................................................................................... 42
Parallel operations .............................................................................................................................................................. 43
10. Recycling the used UPS or batteries ............................................................................................................................. 45
11. Dimensional drawings ..................................................................................................................................................... 47
12. Technical data ..................................................................................................................................................................... 48
Standards ............................................................................................................................................................................ 48
Environment ......................................................................................................................................................................... 48
Mechanical conïŹguration ................................................................................................................................................. 48
Characteristics .................................................................................................................................................................... 48
AC input ................................................................................................................................................................................ 49
DC circuit .............................................................................................................................................................................. 49
AC output .............................................................................................................................................................................. 49
13. Warranty ............................................................................................................................................................................... 50
Produktspezifikationen
Marke: | Eaton |
Kategorie: | Unterbrechungsfreies Stromversorgungssystem |
Modell: | Powerware 9355-12-N-8-32x9Ah |
Breite: | 305 mm |
Tiefe: | 702 mm |
Gewicht: | 160000 g |
Produktfarbe: | Schwarz |
Akku-/Batterietyp: | 9Ah |
Höhe: | 817 mm |
Zertifizierung: | IEC 62040-2, IEC 62040-3 |
GerÀuschpegel: | 50 dB |
Formfaktor: | Tower |
Ausgangsleistung: | 10800 W |
Eingangsfrequenz: | 45/65 Hz |
Anzahl serielle AnschlĂŒsse: | 1 |
Sicherheit: | IEC 62040-1, IEC 60950-1 |
Leistungsfaktor: | 0.9 |
Effizienz: | 98 % |
Anzahl der AC-AusgÀnge: | - AC-AusgÀnge |
Eingangs-Betriebsspannung (min): | 220 V |
Eingangs-Betriebsspannung (max): | 415 V |
AusgangskapazitÀt: | 12 kVA |
Ausgangs-Betriebsspannung (min): | 220 V |
Ausgangs-Betriebsspannung (max): | 415 V |
Typische Backup-Zeit bei halber Belastung: | - min |
Typische Backup-Zeit bei voller Belastung: | - min |
Anzahl der Eingangs-Phasen: | 3 |
Eingangs-Leistungsfaktor: | 0.99 |
Eingangsstrom Gesamtverzerrungsfaktor THD: | 4.5 % |
Anzahl der Ausgangs-Phasen: | 3 |
Brauchst du Hilfe?
Wenn Sie Hilfe mit Eaton Powerware 9355-12-N-8-32x9Ah benötigen, stellen Sie unten eine Frage und andere Benutzer werden Ihnen antworten
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem Eaton
12 Mai 2024
20 MĂ€rz 2024
6 MĂ€rz 2024
Bedienungsanleitung Unterbrechungsfreies Stromversorgungssystem
- Unterbrechungsfreies Stromversorgungssystem Approx
- Unterbrechungsfreies Stromversorgungssystem HP
- Unterbrechungsfreies Stromversorgungssystem Voltcraft
- Unterbrechungsfreies Stromversorgungssystem Siemens
- Unterbrechungsfreies Stromversorgungssystem Schneider
- Unterbrechungsfreies Stromversorgungssystem Lenovo
- Unterbrechungsfreies Stromversorgungssystem Tripp Lite
- Unterbrechungsfreies Stromversorgungssystem Adj
- Unterbrechungsfreies Stromversorgungssystem JUNG
- Unterbrechungsfreies Stromversorgungssystem Block
- Unterbrechungsfreies Stromversorgungssystem Digitus
- Unterbrechungsfreies Stromversorgungssystem APC
- Unterbrechungsfreies Stromversorgungssystem CyberPower
- Unterbrechungsfreies Stromversorgungssystem EnerGenie
- Unterbrechungsfreies Stromversorgungssystem Furman
- Unterbrechungsfreies Stromversorgungssystem Riello
- Unterbrechungsfreies Stromversorgungssystem Steren
- Unterbrechungsfreies Stromversorgungssystem Puls Dimension
- Unterbrechungsfreies Stromversorgungssystem Atlantis Land
- Unterbrechungsfreies Stromversorgungssystem Phoenix Contact
- Unterbrechungsfreies Stromversorgungssystem Middle Atlantic
- Unterbrechungsfreies Stromversorgungssystem Minuteman
- Unterbrechungsfreies Stromversorgungssystem Salicru
- Unterbrechungsfreies Stromversorgungssystem Maruson
- Unterbrechungsfreies Stromversorgungssystem Minute Man
- Unterbrechungsfreies Stromversorgungssystem DEXP
- Unterbrechungsfreies Stromversorgungssystem Bxterra
- Unterbrechungsfreies Stromversorgungssystem Altronix
- Unterbrechungsfreies Stromversorgungssystem FSP
- Unterbrechungsfreies Stromversorgungssystem PowerWalker
- Unterbrechungsfreies Stromversorgungssystem FSP/Fortron
Neueste Bedienungsanleitung fĂŒr -Kategorien-
22 Juni 2024
22 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024
20 Juni 2024